2008-10-27 15:56:55BUILDING PLAN REVIEW
 PERMIT: 07090034
 ADD: 314 10TH STREET
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1307
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 SHEETS A-01/A-02/A-03/A-04/A-05/A-08 AND SHEETS S-1 -
 S-4.
  
 1) SHEETS A-03 AND A-04 SHOW DORMERS ON THE ELEVATIONS
 PLANS. THESE DORMERS ARE NOT SHOWN ON THE PERMITTED SET
 OF DRAWINGS. IF THE DORMERS WILL BE INSTALLED, PROVIDE
 THE STRUCTURAL FRAMING DETAILS SHOWING THE ATTACHMENT
 METHODS FOR THE DORMERS; THE PLANS ALSO SHOW EIFS
 OUTRIGGERS BUT NO INFORMATION OR DETAILS HOW THEY WILL
 BE ATTACHED TO THE STRUCTURE. THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS, COMPUTATIONS, DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 OF SYSTEMS. 106.1.2.
  
 2) SHEET A-05 MAKES REFERENCE TO DETAIL #3 / S-2, THE
 DETAIL ON S-2 DO NOT CORRESPOND WITH SECTION INDICATED
 ON SHEET A-05. THE NEW PLANS ALSO SHOW TWO LAYERS R-21
 INSULATION AND 3? CONTINUOUS SCREEN VENTS ON SHEET A-05
 #4 THEN, ON SHEET S-4 #1 THE INSULATION SHOWN IS R30
 AND THE SCREEN VENTS ARE 7? X 25? SPACED 8? O/C. THE
 DETAILS ALSO FAIL TO SHOW THE EIFS AS INDICATED ON THE
 ELEVATION DRAWINGS. CLARIFY.
  
 NOTE: PLEASE MAKE SURE THE DETAILS AND INFORMATION
 CORRESPOND WITH THE PLANS. SHOP DRAWINGS WILL BE
 REQUIRED FOR THE NEW FLOOR SYSTEM.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726