Date |
Text |
2008-07-28 15:12:44 | |
| ** FAILED REVIEW ** |
| |
| |
| 1) NOTE:EGRESS LIGHTING FOR STAIR #2 DOES NOT MEET |
| THE LIFE SAFETY CODE. 7.9.2.1,7.9.2.2 THE LIGHTING FOOT |
| CANDLES LEVEL IS SHOWING LEVELS FROM .09, .08, .07 AND |
| THEN UP TO 15.3, 14.1 ETC. THIS IS NOT POSSIBLE AS THE |
| SINGLE BATTERY BACK UP FIXTURE IS AT THE TOP OF THE |
| STAIRS. ALSO SHOWS TAKING ALLOWANCE AVERAGE FROM THE |
| INTERIOR LIGHTING WHICH IS NOT PERMITTED. |
| CALLED AND SPOKE TO ENGINEER MR. FORMICA AND HE WILL |
| CALL BACK ONCE HE OBTAINS INFORMATION FROM STAFF. |
| LIGHTING LEVELS ON ALL STAIRS ARE IN QUESTION. THE |
| LIGHTING LUMENS UNDER CONDITIONS OF NORMAL AND |
| EMERGENCY ARE TO BE VERIFIED. |
| |
| 2) NOTE: TYPE SA FIXTURES INDICATE 210WATTS ON SITE |
| PLANS. THE IDR OF THE ENERGY CALCULATIONS STATE 175W. |
| THE FIXTURE WATTAGE NOT BULB IS REQUIRED TO BE USED PER |
| 13-415.2.ABC.1.3. |
| THIS WILL ALSO BE GONE OVER. |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |