Plan Review Notes
Plan Review Notes For Permit 07090034
Permit Number 07090034
Review Stop E
Sequence Number 4
Notes
Date Text
2008-07-28 15:12:44 
 ** FAILED REVIEW **
  
  
 1) NOTE:EGRESS LIGHTING FOR STAIR #2 DOES NOT MEET
 THE LIFE SAFETY CODE. 7.9.2.1,7.9.2.2 THE LIGHTING FOOT
 CANDLES LEVEL IS SHOWING LEVELS FROM .09, .08, .07 AND
 THEN UP TO 15.3, 14.1 ETC. THIS IS NOT POSSIBLE AS THE
 SINGLE BATTERY BACK UP FIXTURE IS AT THE TOP OF THE
 STAIRS. ALSO SHOWS TAKING ALLOWANCE AVERAGE FROM THE
 INTERIOR LIGHTING WHICH IS NOT PERMITTED.
 CALLED AND SPOKE TO ENGINEER MR. FORMICA AND HE WILL
 CALL BACK ONCE HE OBTAINS INFORMATION FROM STAFF.
 LIGHTING LEVELS ON ALL STAIRS ARE IN QUESTION. THE
 LIGHTING LUMENS UNDER CONDITIONS OF NORMAL AND
 EMERGENCY ARE TO BE VERIFIED.
  
 2) NOTE: TYPE SA FIXTURES INDICATE 210WATTS ON SITE
 PLANS. THE IDR OF THE ENERGY CALCULATIONS STATE 175W.
 THE FIXTURE WATTAGE NOT BULB IS REQUIRED TO BE USED PER
 13-415.2.ABC.1.3.
 THIS WILL ALSO BE GONE OVER.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  