2008-05-23 14:23:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 3-4-08 NOTE #1. THE WALL
 BETWEEN THE FIRST FLOOR MECHANICAL ROOM AND LOBBY IS
 FIRE RATED, THE 14X12 SUPPLY AIR DUCT PENETRATING THE
 WALL NEEDS A FIRE DAMPER, PER 2004 FBC/M 607.5.3 OR
 MEET THE EXCEPT.
  
 2) AS NOTED IN LAST REVIEW 3-4-08 NOTE #2. THE 16"
 FLEXIBLE RETURN AIR DUCT MAY NOT PASS THROUGH THE FIRE
 RATED WALL, PER 2004 FBC/M 607.7, PLEASE CORRECT.
  
 3) SEE ELECTRICAL REVIEW NOTE #1 REGARDING THE ENERGY
 CALCULATIONS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]