Date Text
2008-06-26 15:55:35MEETING HELD 6/26/08
 IT BECAME APPARENT OF THE TWO ROLLS OF REVISED NEW SETS
 OF PLANS SUBMITTEDONLY ONE ROLL CONTAINED NEW REVISED
 SHEETS. THE OTHER ROLL WAS NOT REVIEWED FOR CODE
 COMPLIANCE.
 THIS WAS AN ADMINISTRATIVE ERROR BY THE CONTRACTORS
 OFFICE.
 IN ATTENDANCE WAS MR. MICHAEL CARP, MR. KENNEDY AND MR.
 ROBERT FORMICA (ELECTRICAL ENGINEER OF RECORD).
2008-05-23 13:02:28** DENIED3RD REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT THE CORRECT VERSION PER FBC 13-400.3.B. THE
 RESPONSE MENTIONS THE WORDING ON THE STATE WEBSITE
 HOWEVER PLEASE READ WHAT IT SAYS. IT STATES THE *ENERGY
 GAUGE SUMMIT VERSIONS 3.0-3.14 WHICH IS IN *VERSION
 2.5* IS ACCEPTABLE. THIS DOES NOT STATE A VERSION 3.0.
 IT IS STILL VERSION 2.5 WHICH INCORPORATES THE OTHER
 PROGRAMS. PLEASE READ THE STATEMENT AS IT CLEARLY
 STATES *IN VERSION 2.5*. THIS WAS EVEN ATTACHED TO
 ENERGY CALCULATIONS SUBMITTED. I HAVE REDLINED AND
 CIRCLED THE LINE IN WHICH THE STATE HAS PARENTHESIS
 AROUND THE WORDING: * GENERATED BY FLA/COM 2004
 COMPUTER PROGRAM, VERSION 2.5*.
 THIS REVIEWER HAS CALLED TWICE TO THE ENGINEER?S FIRM
 TO GO OVER THIS REQUIREMENT ON THIS AND OTHER PROJECTS.
 NO RETURN CALL HAS BEEN RECEIVED.
 PLEASE KNOW THIS WAS AND HAS BEEN CONFIRMED WITH THE
 FLORIDA BUILDING COMMISSION/DEPARTMENT OF COMMUNITY
 AFFAIRS ON SEVERAL OCCASIONS.
 PLEASE BE SURE OWNER AGENT IS FILLED OUT ON
 CERTIFICATION SHEET.
  
 *** PLEASE SEE SHEET E2.01 WHICH INDICATES INTERIOR
 LIGHTING POWER ALLOWANCE WHICH INDICATES *BUILDING
 METHOD A*. THIS IS NOT POSSIBLE FOR A SHELL BUILDING.
 PLEASE SEE13-101.1.6.
  
 2) NOTE: PLEASE SEE THE SUBMITTED METHOD *B* DOES NOT
 COMPLY WITH THE MINIMUM REQUIRED BY CODE.
 PLEASE SEE SOME OF THE FOLLOWING ARE GIVEN AS
 EXAMPLES.
 FOR EXAMPLE:
 PLEASE BE SURE TO INCLUDE ANY *ASSUMPTIONS* FOR FUTURE
 SHELL SPACE AT A MINIMUM. ONLY SHOWS 4 LIGHT FIXTURES
 AT 64WATTS.
 FOR EXAMPLE:
 PLEASE SEE SOME FIXTURES SHOWN WITH A *0* VALUE. HOW IS
 THIS POSSIBLE?
 FOR EXAMPLE:
 PLEASE SEE EXTERIOR LIGHTING ON THE INPUT DATA REPORT
 AS THESE STILL DO NOT MATCH/CORRELATE WITH THE PLANS.
 THE IDR SHOWS 2-50W FIXTURES AND 1-32 WATT FIXTURE. HOW
 IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW SEVERAL
 OTHER FIXTURES WHICH HAVE NOT BEEN FIGURED OR PLACED
 INTO THE IDR. WHERE ARE THE *J* FIXTURES, THE *C*
 FIXTURES, THE *SA* FIXTURES?????
 FOR EXAMPLE:
 IN SPACE ON FIRST FLOOR WHICH IS SHOWN IN ZONE OTHER
 THAN SHELL ONLY FOUR (4) FIXTURES TOTAL ARE BEING SHOWN
 HOWEVER BASED ON THE FIRST FLOOR LIGHTING ELECTRICAL
 PLANS THERE ARE CLEARLY MORE FIXTURES.
 FOR EXAMPLE:
 PLEASE COORDINATE ALL FIXTURES AND DESIGNATIONS. ONE OF
 THESE WOULD BE *C* FIXTURE WHICH CLEARLY INDICATES THIS
 FIXTURE AS A *RESTROOM FIXTURE* ON THE FIXTURE LEGEND.
  
 **THESE ARE NOT THE ONLY LIGHTS ON PLANS WHICH STILL DO
 NOT COORDINATE WITH THE INPUT DATA REPORT AND ENERGY
 CALCULATIONS.
 THESE ARE ONLY A FEW EXAMPLES OF NON-COMPLIANCE.THIS
 IS NOT AN EXHAUSTED LIST.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SUBMIT *MINIMUM* LIFE SAFETY
 PHOTO-METRICS SHOWING AT LEAST THE MINIMUM COMPLIANCE
 WITH THE LIFE SAFETY CODE NFPA-101 7.8.1.3, 7.9.2.2
 PLEASE SEE THE LIGHTING LEVELS SUBMITTED FOR SOME AREAS
 ARE NOT CODE COMPLIANT AND PLEASE SEE SOME AREAS LIKE
 EXTERIOR REQUIRED EGRESS STAIRS STILL DO NOT SHOW ANY
 LEVELS AT ALL.
 PLEASE SEE PLANS AND COORDINATE.
  
 4) NOTE: PLEASE SEE OTHER SHEETS IN SETS INCLUDING SITE
 LIGHTING ELECTRICAL NOW SHOW THE 2ND FLOOR EXTERIOR
 STAIRS OUT AND AWAY FROM THE BUILDING. THIS WILL AFFECT
 NOT ONLY THE REQUIRED PHOTO-METRICS HOWEVER ALSO THE
 LIGHTING ON ENERGY CALCULATIONS.
 PLEASE BE SURE TO COORDINATE ALL OF THESE SHEETS FOR
 LIFE SAFETY ETC. THIS IS A MINIMUM CODE.
 LS 101 7.8, 7.9, FBC CHAPTER 10,
 FBC ADMIN SECTIONS 106.1.2, FOR COORDINATION.
 FAC 61G15-33.004
  
 5) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING CONTROLS
 HAS NOT BEEN MET. PLEASE SEE 13-415.1.ABC.1.4 ALONE FOR
 EXTERIOR LIGHTING. NOTE #1 ON SHEET E2.01 FOR EXAMPLE
 WHICH STILL SHOWS EXTERIOR LIGHTING TO BE THROUGH
 LIGHTING CONTROL PANEL BUT NO DETAIL FOR ASTRONOMICAL
 TIME CLOCK OR PHOTO-SENSOR CONTROLS.
 RESPONSE MENTIONS THIS WAS REVISED HOWEVER BASED ON THE
 PLANS SUBMITTED THIS WAS NOT THE CASE.
 PLEASE BE SURE TO SEE THE OTHER LIGHTING AS NOTED ON
 PREVIOUS REVIEW FOR INTERIOR LIGHTING ALSO. PLEASE SEE
 SEVERAL AREAS AS NOTED ON PREVIOUS REVIEW IN WHICH
 STANDARD SWITCHES ARE BEING SHOWN. 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 FRAMING MEMBERS AND BONDING AS REQUIRED PER FBC 2704
 RESPONSE MENTIONS THIS WAS ADDED TO E3.01 HOWEVER THIS
 IS NOT THE CASE.
  
 7) NOTE: PLEASE SEE RISER STILL ONLY SHOWS 3-MAINS WHEN
 IN FACT THERE ARE 4 MAINS. PLEASE LABEL ACCORDINGLY.
 PLEASE LABEL: 1OF4, 2OF 4 ETC
 230.2E.
  
 8) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENT FOR CODE
 COMPLIANCE. THIS FEE AS REQUIRED BY STATUTORY
 REQUIREMENT HAS NOW BEEN ASSESSED. IT IS REQUIRED UNDER
 STATE STATUTE AND IS REQUIRED TO BE PAID BEFORE PLANS
 MAY BE RESUBMITTED FOR THE NEXT REVIEW. IT IS IMPORTANT
 TO KNOW ONE SET OF PLANS ARE RETAINED BY THIS OFFICE AT
 THIS TIME. IT IS ALSO IMPORTANT TO KNOW THAT IF THERE
 ARE ANY QUESTIONS, OR ANY PART OF THE REVIEW COMMENTS
 ARE NOT UNDERSTOOD IN ANY WAY, PLEASE CALL OR CONTACT
 THIS OFFICE.
 THIS REVIEW CALLED AND LEFT TWO MESSAGES IN RECENT
 WEEKS FOR RETURN CALLS TO BE MADE HOWEVER THIS TO DATE
 NO CALLS HAVE BEEN RECEIVED.
 THIS FEE UNDER STATUE IS DUE BEFORE RESUB. $9,000.00
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  