2008-05-14 12:01:57 | REVIEW #3 |
| BUILDING PLAN REVIEW #3 |
| PERMIT: 07090034 |
| ADD: 314 10TH ST |
| CONT: KENNEDY CONTRACTORS, INC. |
| TEL: (561)434-1300 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RD REVIEW 5-12-08 |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B) OK |
| 1C) OK |
| |
| 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E)OK. |
| 2)OK |
| |
| **SECOND REQUEST.** NOTED |
| 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6. |
| |
| 4) OK |
| 5) OK |
| 6) OK |
| 7) OK |
| 8) OK |
| 9) OK |
| 10)OK |
| 11) OK |
| 12) OK |
| 13). OK |
| 14)OK |
| 15) OK |
| 16) OK |
| 17)OK |
| 18) OK |
| 19)OK |
| 20) OK |
| |
| **THE AMOUNT AND TYPE OF DOORS INDICATED IS INCORRECT, |
| THE INSULATION ON THE PLANS DIFFERS FROM THE ENERGY |
| CALCS, THE TYPE OF ROOF IS DIFFERENT: THE ENERTY CALCU |
| SHOWS BUILT-UP GRAVEL THE PLANS SHOW METAL** |
| 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE |
| RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND |
| WALL FACE, AS WELL AS DOORS. THE NUMBER OF EXTERIOR |
| DOORS WAS NOT FILLED IN! 106.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 22)OK |
| 23) OK |
| |
| 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING |
| PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) SINGLE HUNG WINDOWS |
| B) FIXED/ STOREFRONT WINDOWS |
| C) MULLIONS VERTICAL OK |
| D) SIDE LUTES |
| E) SWING GLAZED DOORS (1) (INDICATE THE DOOR TO BE |
| INSTALLED) |
| F) EXTERIOR HOLLOW METAL SWING DOORS (4) CHECK ENERGY |
| CALCS. |
| G) TRUSS ANCHORS OK |
| H) ROOF ASSEMBLIES FL#704-R1 IS MISSING THE SEAM-LOC |
| REPORT |
| |
| 25)OK |
| 26) OK |
| 27) REMOVED |
| 28) OK |
| 29)OK |
| 30)OK |
| 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |
| ** SUBMIT A WINDOW SCHEDULE SHOWING THE HEIGHT AND |
| WIDTH OF EACH WINDOW** |
| |
| MYRON JACOBS. |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6726 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |