Plan Review Notes
Plan Review Notes For Permit 07090034
Permit Number 07090034
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-14 09:22:24DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 THE FOLLOWING COMMENTS ARE NUMBERED RO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET
 DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH
 FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA
 THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE.
 PLEASE INDICATE TURNING AREA.
 **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT
 COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR
 THE BREAKROOM.
  
 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5
 FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS,
 AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO
 THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.--
 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION
 11-4.19.2. 28" IS SHOWN.
 **RESPONSE NOTED HOWEVER THERE ARE STILL ISSUES ON THE
 DETAIL WITH THE FOLLOWING: 11-4.16.5 FLUSH CONTROLS
 (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS (LEVER TYPE, PUSH
 TYPE, AND ELECTRONICALLY CONTROLED MECHANISMS ARE
 EXAMPLES OF ACCEPTABLE DESIGN). PLEASE INDICATE THESE
 REQUIRED ITEMS ON THE PLANS.
  
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED.
  
 8. **OK** COMMENT ADDRESSED.
  
 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER
 HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS
 INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE.
 SECTION 13-103.
 **RESPONSE NOTED, HOWEVER THE WRONG FORM (400A) IS
 BEING USED. THIS IS NOT A WHOLE BUILDING WITH THE FIRST
 FLOOR BEING A SHEEL BY INDICATING FUTURE LEASABLE
 SPACE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved