Date |
Text |
2008-03-14 09:22:24 | DENIED 2ND TIME |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED RO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. **OK** COMMENT ADDRESSED. |
| |
| 2. **OK** COMMENT ADDRESSED. |
| |
| 3. **OK** COMMENT ADDRESSED. |
| |
| 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. |
| SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET |
| DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH |
| FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA |
| THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. |
| PLEASE INDICATE TURNING AREA. |
| **RESPONSE NOTED, HOWEVER THE TURNING AREA THAT |
| COMPLIES WITH SECTION 11-4.2.3 WAS NOT INDICATED FOR |
| THE BREAKROOM. |
| |
| 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 |
| FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, |
| AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO |
| THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- |
| 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION |
| 11-4.19.2. 28" IS SHOWN. |
| **RESPONSE NOTED HOWEVER THERE ARE STILL ISSUES ON THE |
| DETAIL WITH THE FOLLOWING: 11-4.16.5 FLUSH CONTROLS |
| (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS (LEVER TYPE, PUSH |
| TYPE, AND ELECTRONICALLY CONTROLED MECHANISMS ARE |
| EXAMPLES OF ACCEPTABLE DESIGN). PLEASE INDICATE THESE |
| REQUIRED ITEMS ON THE PLANS. |
| |
| 6. **OK** COMMENT ADDRESSED. |
| |
| 7. **OK** COMMENT ADDRESSED. |
| |
| 8. **OK** COMMENT ADDRESSED. |
| |
| 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER |
| HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS |
| INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. |
| SECTION 13-103. |
| **RESPONSE NOTED, HOWEVER THE WRONG FORM (400A) IS |
| BEING USED. THIS IS NOT A WHOLE BUILDING WITH THE FIRST |
| FLOOR BEING A SHEEL BY INDICATING FUTURE LEASABLE |
| SPACE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |