2008-03-04 17:43:59PLANS DENIED
 1)PAGE A-01 SHOWS MECHANICAL ROOM RATED .PAGE M1.01
 SHOWES DUCT PENETRETEING MECHANICAL ROOM WALL . PLAESE
 SEE SECTION 607.5 2004 FBC (M) WHERE REQUIRED .
 2)FLEX AND T-FIN CAN NOT PENETRATE A RATED WALL .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732