Plan Review Notes For Permit 07090034 |
Permit Number |
07090034 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-03-04 17:43:59 | PLANS DENIED | | 1)PAGE A-01 SHOWS MECHANICAL ROOM RATED .PAGE M1.01 | | SHOWES DUCT PENETRETEING MECHANICAL ROOM WALL . PLAESE | | SEE SECTION 607.5 2004 FBC (M) WHERE REQUIRED . | | 2)FLEX AND T-FIN CAN NOT PENETRATE A RATED WALL . | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|