2008-02-11 09:10:59 | *** DENIED 2ND REVIEW *** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| MAY NOT USE METHOD *A*. THIS BUILDING CONTAINS A SHELL |
| AND ASSUMPTIONS ARE TO BE MADE. PLEASE SEE 13-400.3.B, |
| WHICH IS FOR VERSION 2.5 AS 3.0 IS NOT YET ADOPTED. |
| PLEASE SEE THIS SAME SECTION AS NOTED FOR SHELL AS WELL |
| AS 13-400.2.A.2. WHICH STATES AS LONG AS ALL DESIGN |
| PARAMETERS ARE KNOWN THEN METHOD *A* CAN BE USED. |
| HOWEVER AT THIS TIME THIS IS NOT POSSIBLE WHEN THE |
| FIRST FLOOR IS STILL SHELL SPACE. |
| THIS WAS MENTIONED TO SEE MECHANICAL COMMENTS ALSO. |
| |
| 2) NOTE: PLEASE BE SURE THE INFORMATION ON THE INPUT |
| DATA REPORT FOR NEW CALCULATIONS COORDINATES WITH |
| PLANS. PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED |
| AS IDR THROUGH THE REST OF THIS COMMENT. |
| A) ** PLEASE SEE THAT ALL LIGHTING FIXTURES ON PLANS |
| COORDINATE WITH THE IDR FOR INTERIOR AND EXTERIOR FOR |
| THE NUMBER OF FIXTURES, THE WATTAGE AND THE METHOD OF |
| CONTROLS. |
| PLEASE SEE FOR EXAMPLE THE METHOD OF CONTROLS FOR SOME |
| ARE NOTED A *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN |
| ALL LIGHTING IS REQUIRED TO HAVE SOME SORT OF AUTOMATED |
| SHUT OFF. |
| PLEASE SEE FOR EXAMPLE THE EXTERIOR LIGHTING ON THE IDR |
| SHOWS A TOTAL OF 1-100W FIXTURE YET THE PLANS CONTAIN |
| MORE THAN 1-100W FIXTURE. THE PLANS ALSO CONTAIN OTHER |
| FIXTURES ON THE EXTERIOR OF BUILDING. PLEASE SEE H |
| FIXTURES, C FIXTURE, J-FIXTURES ETC. |
| PLEASE SEE THE INTERIOR LIGHTING AS NOTED ON TABLE ON |
| E2.01 DOES NOT COORDINATE WITH THE IDR ON CALCULATIONS |
| FOR THE COUNT OF FIXTURES. THE IDR FOR INTERIOR |
| LIGHTING DOES SEEM OK. PLEASE SEE NOTES ABOVE AS METHOD |
| WILL STILL CHANGE. |
| |
| 3) NOTE: AS NOTED ON PREVIOUS PLANS ZONING REQUIRES A |
| MINIMUM LIGHTING LEVELS FOR PARKING AREAS, YET NO |
| EXTERIOR SITE LIGHTING IS SHOWN ON PLANS. THIS WILL BE |
| CONFIRMED WITH ZONING. IF REQUIRED PLEASE BE SURE TO |
| FOLLOW CONTROLS REQUIRED IN CHAPTER 13 AS WELL AS |
| INCLUDING IN IDR. |
| |
| 4) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING |
| REQUIRED LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2, |
| .1.3 AND .1.4. |
| A) **PLEASE SEE EXTERIOR LIGHTS NOTE MENTIONS LIGHTING |
| TO BE THROUGH LCP, YET NO INFORMATION IS PROVIDED ON |
| TYPE OF TIME CLOCK, BATTERY BACK UP OF POWER ETC. |
| PLEASE SEE CODE SECTION 13-415.1.ABC.1.4 WHICH REQUIRES |
| ONE OF TWO METHODS (BOTH COULD BE DONE ALSO). |
| EITHER PHOTO-SENSOR OR ASTRONOMICAL TIME CLOCK WITH |
| BATTERY BACK UP OF A MINIMUM OF 10HRS. |
| |
| B) ** PLEASE SEE SOME AREAS WHERE STANDARD SWITCHES ARE |
| STILL BEING SHOWN. (LOBBY) |
| C) ** PLEASE SEE NO MAXIMUM TIMES COULD BE LOCATED ON |
| PLANS FOR ANY OF THE LIGHTING CONTROL DEVICES AS WELL |
| AS THE MAXIMUM TIMES FOR OVER RIDES. |
| D) ** PLEASE SEE NO SCHEDULING COULD BE LOCATED ON |
| PLANS. |
| E) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| CERTIFICATION SHEETS. 13-103.1.1.1 |
| |
| 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO |
| EGRESS LIGHTING FOR STAIRS UNDER NORMAL AND EMERGENCY. |
| THE PHOTO-METRICS SUBMITTED WERE ONLY FOR LEVELS UNDER |
| EMERGENCY FOR STAIR #1. NO LEVELS UNDER EITHER NORMAL |
| OR EMERGENCY WERE LOCATED FOR STAIR #2. |
| PLEASE SEE 7.8.1.3 OF LS 101 WHICH REQUIRES 10FT |
| CANDLES UNDER NORMAL AND 7.9.2 WHICH ALLOWS LEVELS DOWN |
| TO 1FT CANDLE UNDER EMERGENCY. |
| PLEASE SUBMIT. |
| FAC 61G15-33.004, |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO A |
| NOTE BEING PLACED ON PLANS FOR ALL METAL FRAMING |
| MEMBERS TO BE BONDED AS REQUIRED PER FBC 2704. |
| |
| 7) NOTE: THE RISER SHOWS 4 MAINS, ONLY THREE LABELED AS |
| MAINS. EACH OF THESE IS NOT NOTED CORRECTLY. ONE SAYS |
| MAIN ONE OF ONE. HOW IS THIS POSSIBLE WHEN THERE ARE |
| FOUR MAINS? TWO ARE LABELED AS MAINS TWO OF THREE AND |
| THREE OF THREE. THIS DOES NOT COORDINATE WITH FIRST |
| MAIN. PLEASE ALSO SEE THE HOUSE MAIN OF SERVICE DOES |
| INDICATE ANY INDICATION OF MAIN ETC. |
| EXAMPLE: 1 OF 4, 2 OF 4, 3 OF 4 AND 4 OF 4. |
| PLANS ON SHEET E1-01 ONLY SHOWS THREE MAINS. WHERE IS |
| THE FOURTH MAIN? |
| PLEASE LABEL MAINS. 230.2E |
| PLEASE SHOW LOCATIONS FOR GROUPING ETC. 230.70, 230.72, |
| 110.26 ETC |
| |
| 8) NOTE: PLEASE SEE NOTICE FOR FS 553.80(2)(B) IS GIVEN |
| ONLY A NOTICE AT THIS TIME AS THERE WERE REPEATED |
| COMMENTS FOR CODE COMPLIANCE FOR SOME OF THE SAME |
| ITEMS. |
| |
| ** PLEASE KNOW AS SOME ITEMS ARE STILL NOT SUBMITTED OR |
| SHOWN, REVIEW OF SOME ITEMS STILL CAN NOT BE DONE. |
| THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| CAN NOT BE MADE AT THIS TIME. |
| |
| ** PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED |
| HOWEVER IS HELPFUL IN THE REVIEW PROCESS. RESPONSES |
| SUBMITTED FOR SOME OF THE OTHER TRADES ONLY. |
| |
| PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY |
| QUESTIONS OR IF THERE ARE ANY COMMENTS ARE NOT TYPED IN |
| A CLEAR FASHION PLEASE DO NOT HESITATE IN CONTACTING |
| THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |