Notes
Date Text
2008-02-11 09:10:59*** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 MAY NOT USE METHOD *A*. THIS BUILDING CONTAINS A SHELL
 AND ASSUMPTIONS ARE TO BE MADE. PLEASE SEE 13-400.3.B,
 WHICH IS FOR VERSION 2.5 AS 3.0 IS NOT YET ADOPTED.
 PLEASE SEE THIS SAME SECTION AS NOTED FOR SHELL AS WELL
 AS 13-400.2.A.2. WHICH STATES AS LONG AS ALL DESIGN
 PARAMETERS ARE KNOWN THEN METHOD *A* CAN BE USED.
 HOWEVER AT THIS TIME THIS IS NOT POSSIBLE WHEN THE
 FIRST FLOOR IS STILL SHELL SPACE.
 THIS WAS MENTIONED TO SEE MECHANICAL COMMENTS ALSO.
  
 2) NOTE: PLEASE BE SURE THE INFORMATION ON THE INPUT
 DATA REPORT FOR NEW CALCULATIONS COORDINATES WITH
 PLANS. PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED
 AS IDR THROUGH THE REST OF THIS COMMENT.
 A) ** PLEASE SEE THAT ALL LIGHTING FIXTURES ON PLANS
 COORDINATE WITH THE IDR FOR INTERIOR AND EXTERIOR FOR
 THE NUMBER OF FIXTURES, THE WATTAGE AND THE METHOD OF
 CONTROLS.
 PLEASE SEE FOR EXAMPLE THE METHOD OF CONTROLS FOR SOME
 ARE NOTED A *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN
 ALL LIGHTING IS REQUIRED TO HAVE SOME SORT OF AUTOMATED
 SHUT OFF.
 PLEASE SEE FOR EXAMPLE THE EXTERIOR LIGHTING ON THE IDR
 SHOWS A TOTAL OF 1-100W FIXTURE YET THE PLANS CONTAIN
 MORE THAN 1-100W FIXTURE. THE PLANS ALSO CONTAIN OTHER
 FIXTURES ON THE EXTERIOR OF BUILDING. PLEASE SEE H
 FIXTURES, C FIXTURE, J-FIXTURES ETC.
 PLEASE SEE THE INTERIOR LIGHTING AS NOTED ON TABLE ON
 E2.01 DOES NOT COORDINATE WITH THE IDR ON CALCULATIONS
 FOR THE COUNT OF FIXTURES. THE IDR FOR INTERIOR
 LIGHTING DOES SEEM OK. PLEASE SEE NOTES ABOVE AS METHOD
 WILL STILL CHANGE.
  
 3) NOTE: AS NOTED ON PREVIOUS PLANS ZONING REQUIRES A
 MINIMUM LIGHTING LEVELS FOR PARKING AREAS, YET NO
 EXTERIOR SITE LIGHTING IS SHOWN ON PLANS. THIS WILL BE
 CONFIRMED WITH ZONING. IF REQUIRED PLEASE BE SURE TO
 FOLLOW CONTROLS REQUIRED IN CHAPTER 13 AS WELL AS
 INCLUDING IN IDR.
  
 4) NOTE: PLEASE SEE SOME AREAS ARE STILL MISSING
 REQUIRED LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2,
 .1.3 AND .1.4.
 A) **PLEASE SEE EXTERIOR LIGHTS NOTE MENTIONS LIGHTING
 TO BE THROUGH LCP, YET NO INFORMATION IS PROVIDED ON
 TYPE OF TIME CLOCK, BATTERY BACK UP OF POWER ETC.
 PLEASE SEE CODE SECTION 13-415.1.ABC.1.4 WHICH REQUIRES
 ONE OF TWO METHODS (BOTH COULD BE DONE ALSO).
 EITHER PHOTO-SENSOR OR ASTRONOMICAL TIME CLOCK WITH
 BATTERY BACK UP OF A MINIMUM OF 10HRS.
  
 B) ** PLEASE SEE SOME AREAS WHERE STANDARD SWITCHES ARE
 STILL BEING SHOWN. (LOBBY)
 C) ** PLEASE SEE NO MAXIMUM TIMES COULD BE LOCATED ON
 PLANS FOR ANY OF THE LIGHTING CONTROL DEVICES AS WELL
 AS THE MAXIMUM TIMES FOR OVER RIDES.
 D) ** PLEASE SEE NO SCHEDULING COULD BE LOCATED ON
 PLANS.
 E) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 CERTIFICATION SHEETS. 13-103.1.1.1
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO
 EGRESS LIGHTING FOR STAIRS UNDER NORMAL AND EMERGENCY.
 THE PHOTO-METRICS SUBMITTED WERE ONLY FOR LEVELS UNDER
 EMERGENCY FOR STAIR #1. NO LEVELS UNDER EITHER NORMAL
 OR EMERGENCY WERE LOCATED FOR STAIR #2.
 PLEASE SEE 7.8.1.3 OF LS 101 WHICH REQUIRES 10FT
 CANDLES UNDER NORMAL AND 7.9.2 WHICH ALLOWS LEVELS DOWN
 TO 1FT CANDLE UNDER EMERGENCY.
 PLEASE SUBMIT.
 FAC 61G15-33.004,
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO A
 NOTE BEING PLACED ON PLANS FOR ALL METAL FRAMING
 MEMBERS TO BE BONDED AS REQUIRED PER FBC 2704.
  
 7) NOTE: THE RISER SHOWS 4 MAINS, ONLY THREE LABELED AS
 MAINS. EACH OF THESE IS NOT NOTED CORRECTLY. ONE SAYS
 MAIN ONE OF ONE. HOW IS THIS POSSIBLE WHEN THERE ARE
 FOUR MAINS? TWO ARE LABELED AS MAINS TWO OF THREE AND
 THREE OF THREE. THIS DOES NOT COORDINATE WITH FIRST
 MAIN. PLEASE ALSO SEE THE HOUSE MAIN OF SERVICE DOES
 INDICATE ANY INDICATION OF MAIN ETC.
 EXAMPLE: 1 OF 4, 2 OF 4, 3 OF 4 AND 4 OF 4.
 PLANS ON SHEET E1-01 ONLY SHOWS THREE MAINS. WHERE IS
 THE FOURTH MAIN?
 PLEASE LABEL MAINS. 230.2E
 PLEASE SHOW LOCATIONS FOR GROUPING ETC. 230.70, 230.72,
 110.26 ETC
  
 8) NOTE: PLEASE SEE NOTICE FOR FS 553.80(2)(B) IS GIVEN
 ONLY A NOTICE AT THIS TIME AS THERE WERE REPEATED
 COMMENTS FOR CODE COMPLIANCE FOR SOME OF THE SAME
 ITEMS.
  
 ** PLEASE KNOW AS SOME ITEMS ARE STILL NOT SUBMITTED OR
 SHOWN, REVIEW OF SOME ITEMS STILL CAN NOT BE DONE.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 ** PLEASE KNOW A RESPONSE LETTER IS NOT REQUIRED
 HOWEVER IS HELPFUL IN THE REVIEW PROCESS. RESPONSES
 SUBMITTED FOR SOME OF THE OTHER TRADES ONLY.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF THERE ARE ANY
 QUESTIONS OR IF THERE ARE ANY COMMENTS ARE NOT TYPED IN
 A CLEAR FASHION PLEASE DO NOT HESITATE IN CONTACTING
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  