Plan Review Notes
Plan Review Notes For Permit 07090034
Permit Number 07090034
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-21 11:28:39 
 BUILDING PLAN REVIEW
 PERMIT: 07090034
 ADD: 314 10TH ST
 CONT: KENNEDY CONTRACTORS, INC.
 TEL: (561)434-1300
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) OK
  
 1C) **NOTE**106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) OK
 2)OK
  
 **2ND REQUEST**
 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6.
  
 **NOTED; HOWEVER, EACH ACCESSIBLE PARKING SPACE MUST BE
 NO LESS THAN 12 FEET WIDE 11-4.6.2 (GREY AREA)**
 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW
 THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE
 AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF
 14.0?.
 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE
 IS A
  
 **NOTED, HOWEVER, THE SECOND MEANS OF EGRESS THE
 INTERIOR STAIRS ALSO REQUIRE AN AREA OF RESCUE
 ASSISTANCE. SHOW COMPLIIANCE.**
 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY
 BUILDINGS NOT HAVING FIRE SPRINKLERS; PLEASE SEE
 11-4.1.3 EXCEPTION# 9.
 IN BUILDINGS OR FACILITIES, OR PORTIONS OF
 BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE
 SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL
 BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT
 FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF
 ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF
 RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL
 (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED
 EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH
 SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE
 REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS,
 SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE
 ASSISTANCE.
 EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED
 IN BUILDINGS OR FACILITIES HAVING A SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR; THERE IS
 NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS
 BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS
 ARE TO BE MET FOR AREAS OF RESCUE ASSISTANCE; PLEASE
 PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS.
 **A SECOND MEANS OF RESCUE ASSISTANCE IS REQUIRED AT
 THE INTERIOR STAIRWAY PER 11-4.1.3 EXCEPTION# 9.**
  
 7) OK
  
 **NOTED, HOWEVER, 11-4.3.11.3 STAIRWAY WIDTH
 EACH STAIRWAY ADJACENT TO AN AREA OF RESCUE ASSISTANCE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF 48 INCHES BETWEEN
 HANDRAILS.
  
 8) OK
 9) OK
 10)OK
  
 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE
 TYPE OF WALL CONFIGURATION TO BE USED.
 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP
 ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT
 SEPARATION WALLS. **THERE ARE NOT DETAILS FOR WALLS
 TYPES 1W/ 3W / 4W/ 5W AND 6W, ALSO SOME OF THE WALLS
 ARE NOT LABELED(TAGGED)** NOTE: PER TABLE 1016.1
 BUSINESS OCCUPANCY CORRIDORS SERVING AN OCCUPANT LOAD
 GREATER THAN 30 WILL REQUIRE A 1HR RATING.
  
 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT
 SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF
 MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING
 OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED
 106.1.2. **THE DETAIL UL P544 IS MISSING THE DRYWALL
 INFORMATION.**
  
 13) OK
  
 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR
 STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM
 THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1,
 ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC
 CODE COMMENTARY. **THE FLOOR PLANS SHOW THE SEPARATION
 OF THE WINDOWS FROM THE STAIRWAY; HOWEVER THE ELEVATION
 DRAWING ON SHEET A-03 SHOWS ONE OF THE WINDOWS WITH IN
 5 FEET OF THE STAIRWAY. THE FLOOR PLANS SHOW SINGLE
 WINDOWS AND THE ELEVATION DRAWINGS SHOWS DOUBLE
 WINDOWS. ANY WINDOW WITHIN 10 FEET OF THE STAIRS SHALL
 HAVE AT LEAST A 1 HOUR FIRE RATING. CLARIFY.**
  
 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE
 RISER NOR TREAD DIMENSION, SEE 1009.3. **THERE IS NO
 SHEET S-06 IN THE PLANS AS STATED IN YOUR RESPONSE
 LETTER.**
  
 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE
 HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED
 THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE
 IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO
 STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2.
 **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR
 RESPONSE LETTER.**
  
 **SHEET A-03 SHOWS TWO ELEVATION DRAWINGS.**
 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE
 USE OF A BREAK ROOM SINKS, THE PLANS DO NOT PROVIDE AN
 ELEVATION OF THIS AREA PLEASE COMPLY WITH THE
 FOLLOWING:
 SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH
 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH
 SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 **THERE IS NO SHEET S-06 IN THE PLANS AS STATED IN YOUR
 RESPONSE LETTER.**
 18) PLANS DO NOT PROVIDE ANY INFORMATION ON
 PENETRATIONS OF HORIZONTAL ASSEMBLIES,
 711.5 PENETRATIONS .PENETRATIONS THROUGH
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 712. 712.4.1.1
 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
 PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE
 FLOOR/ CEILING ASSEMBLY.
  
  
 **2 REQUEST**
 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE
 BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY
 ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE
 EITHER ?B? OR ?C?.
 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST
 FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH,
 METHOD ?A? CAN NOT BE USED.
  
  
 20) OK
  
 **2 REQUEST**
 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE
 RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND
 WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE
 NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2
 ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS
 SHALL BE.
  
 **PROVIDE INFORMATION ON THE RIDGE VENT SYSTEM.**
 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES AN EXTERIOR
 WALL AND ROOF SECTION. THE PLANS NEED TO SHOW
 COMPLIANCE WITH : 1203.250 PERCENT OF THE REQUIRED
 VENTILATING AREA PROVIDED BY VENTILATORS LOCATED IN THE
 UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS.
  
 **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE
 STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE
 SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.**
 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING
 PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) SINGLE HUNG WINDOWS
 B) FIXED/ STOREFRONT WINDOWS
 C) MULLIONS VERTICAL
 D) SIDE LITES
 E) SWING GLAZED DOORS
 F) EXTERIOR HOLLOW METAL SWING DOORS
 G) TRUSS ANCHORS
 H) ROOF ASSEMBLIES
  
  
 **SOME OF THE PRODUCT APPROVALS ARE STILL MISSING THE
 STATE COVER SHEETS. PLEASE CIRCLE OR HI-LIGHT THE
 SYSTEM OR ITEM TO BE USED FROM EACH PRODUCT.**
 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 26) OK
 27) **DORMER DELETED**
  
 **2REQUEST**
 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE
 UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE?
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 29)OK
 30)OK
  
 **2 REQUEST**
 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS.
 BUILDING PLAN REVIEW
 TEL: (561)805-6726
 FAX: (561)659-8026
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved