Notes
Date Text
2007-10-23 13:40:05ZONING REVIEW: FAILED
  
 ** MEETING TO BE HELD WITH APPLICANT ON 10/24/07 TO
 REVIEW IN MORE DETAIL ZONING COMMENTS**
 COMMENTS BELOW ARE PRELIMINARY PRIOR TO MEETING.
  
 1) PLEASE REVISE DRIVEWAY AND PARKING ARRANGEMENT.
 DRIVEWAY TO BE REDUCED TO 12'-0" IN WIDTH WITH PARALLEL
 PARKING SPACES A MINIMUM OF 8'-6" WIDE
 2) ADA SPACE TO BE RELOCATED; MINIMUM WIDTH IS 8'-6"
 WITH 5'-0" ACCESS AISLE
 3) SIDEWALK SHALL BE PROVIDED FROM SIDE ENTRY TO PUBLIC
 SIDEWALK SO THAT IT IS NOT NECESSARY TO WALK DOWN
 DRIVEWAY OR THROUGH PARKING SPACES
 4) AT REAR, PLEASE MOVE TRASH ENCLOSURE AREA TO WESTERN
 CORNER OF SITE; STANDARD CITY DETAILS FOR ENCLOSURE
 SHOULD BE PROVIDED; ELEVATIONS SHOULD BE PROVIDED
 5) LANDSCAPE PLAN DOES NOT MATCH ARCH SITE PLAN OR
 ELEVATIONS; DOOR IS SHOWN ON NORTH ELEVATION, BUT
 CANNOT EXIT OUT INTO LANDSCAPE AREA; PLEASE REVISE
 6) NORTH ELEVATION SHALL BE REVISED AND TREATED AS A
 "FRONT" ELEVATION WITH APPROPRIATE DETAILS, INCLUDING
 PORCHES, RAILINGS, ETC. WHERE NECESSARY; SEE EAST
 ELEVATION FOR DETAILS TO BE USED.
 7) "FRONT" DOOR ON NORTH ELEVATION SHOULD BE CONNECTED
 TO PUBLIC SIDEWALK, EITHER DIRECTLY, OR CONNECTING TO
 ITEM (3) ABOVE.
 8) PLEASE REDUCE PITCH OF ROOF TO 3/12 OR 4/12 TO
 BETTER MATCH SCALE OF BUILDING.
 9) PLEASE PROVIDE BUILDING SECTION; ARE DORMER WINDOWS
 REAL OR FAKE? IS THERE ANY INTENTION TO USE THIS THIRD
 LEVEL FOR OFFICE OR RESIDENTIAL SPACE?
  
 MATT FLIS - 822-1445