Plan Review Notes
Plan Review Notes For Permit 07090034
Permit Number 07090034
Review Stop P
Sequence Number 1
Notes
Date Text
2007-11-03 06:53:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. CODE ADOPTED IS THE FBC-2004 W/2006 REVISIONS.
 PLEASE INDICATE THAT PLANS WERE DESIGNED TO THESE
 CODES.
  
 2. THE ADDRESS ON THE COVER SHEET, SHT LA-1 & SHT SP-1
 DOES NOT CORRELATE WITH THE ADDRESS ON THE OTHER
 SHEETS, THE APPLICATION AND THE ADDRESS ON OUR SYSTEM.
 PLEASE CORRELATE THE ADDRESS ON THESE SHEETS. SECTION
 106.1.1.
  
 3. SHT LA-1 THE CERTIFICATE OF AUTHROIZATION, (FIRM
 LICENSE NUMBER), IS MISSING FROM THE TITLE BLOCK FOR
 DIXIE LANDSCAPE. FAC 61G1-16.004(2) & FS 481.306.
  
 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET
 DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH
 FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA
 THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE.
 PLEASE INDICATE TURNING AREA.
  
 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5
 FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS,
 AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO
 THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.--
 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION
 11-4.19.2. 28" IS SHOWN.
  
 6. SHT A-02 DETAIL 1. SHOW THE W/C'S TO BE 18" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28), AND
 THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30"
 MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE REQUIRED
 FOR THE LAV. SECTION 11-4.19.3.
  
 7. SUBMIT A SECOND FLOOR PLUMBING PLAN SHOWING THE
 LOCATION OF ALL FIXTURES, SANITARY PIPING, VENTS, WATER
 LINES ETC. SECTION 106.3.5.1.3(1)(2)(3)(4)(5)(6)(10).
  
 8. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE
 EEMAX INSTA-HOT WATER HEATER. SPECIFICATION SHEETS
 SHALL SHOW THE LISTING FOR THE WATER HEATER.
  
 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER
 HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS
 INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE.
 SECTION 13-103.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  