2007-11-03 06:53:14 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. CODE ADOPTED IS THE FBC-2004 W/2006 REVISIONS. |
| PLEASE INDICATE THAT PLANS WERE DESIGNED TO THESE |
| CODES. |
| |
| 2. THE ADDRESS ON THE COVER SHEET, SHT LA-1 & SHT SP-1 |
| DOES NOT CORRELATE WITH THE ADDRESS ON THE OTHER |
| SHEETS, THE APPLICATION AND THE ADDRESS ON OUR SYSTEM. |
| PLEASE CORRELATE THE ADDRESS ON THESE SHEETS. SECTION |
| 106.1.1. |
| |
| 3. SHT LA-1 THE CERTIFICATE OF AUTHROIZATION, (FIRM |
| LICENSE NUMBER), IS MISSING FROM THE TITLE BLOCK FOR |
| DIXIE LANDSCAPE. FAC 61G1-16.004(2) & FS 481.306. |
| |
| 4. SHT A-01 THE BREAKROOM SINK SHALL BE ACCESSIBLE. |
| SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| SUBSECTIONS. FORWARD APPROACH REQUIRED AND CABINET |
| DOORS ARE NOT APPROVED. PLEASE PROVIDE A DETAIN WITH |
| FRONTAL ELEVATION SHOWING COMPLIANCE. A TURNING AREA |
| THAT COMPLIES WITH SECTION 11-4.2.3 SHALL BE PROVIDE. |
| PLEASE INDICATE TURNING AREA. |
| |
| 5. SHT A-02 DETAIL A. SHOW COMPLIANCE WITH 11-4.16.5 |
| FLUSH CONTROLS, (WIDE SIDE OF W/C), 11-4.19.5 FAUCETS, |
| AND SHOW THE W/C TO BE 18" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE, (FIG. 28).--HEIGHT TO |
| THE TOP OF THE LAV IS NOT LEGIBLE. PLEASE CLARIFY.-- |
| 29" KNEE CLEARANCE IS REQUIRED AT THE LAV PER SECTION |
| 11-4.19.2. 28" IS SHOWN. |
| |
| 6. SHT A-02 DETAIL 1. SHOW THE W/C'S TO BE 18" OFF THE |
| WALL TO THE CENTERLINE OF THE FIXTURE, (FIG 28), AND |
| THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE TO BE CENTERED ON THE 30" |
| MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE REQUIRED |
| FOR THE LAV. SECTION 11-4.19.3. |
| |
| 7. SUBMIT A SECOND FLOOR PLUMBING PLAN SHOWING THE |
| LOCATION OF ALL FIXTURES, SANITARY PIPING, VENTS, WATER |
| LINES ETC. SECTION 106.3.5.1.3(1)(2)(3)(4)(5)(6)(10). |
| |
| 8. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE |
| EEMAX INSTA-HOT WATER HEATER. SPECIFICATION SHEETS |
| SHALL SHOW THE LISTING FOR THE WATER HEATER. |
| |
| 9. THE ENERGY CALCULATIONS SHALL REFLECT THE WATER |
| HEATER SPECIFIED, (INSTA-HOT MODEL). THE CALCULATIONS |
| INDICATE A 20 GAL WATER HEATER. THESE DO NOT CORRELATE. |
| SECTION 13-103. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |