2007-10-29 11:20:00PLAN DENIED
 1- PLEASE REFER TO SECTION 502.7.3.6 TERMINATION POINT
 # 2 (OUT DOOR AIR AND CONDENSORS ) PAGE M1.01.
 2- PLEASE REFER TONFPA 101 SECTION 7.1.3.2.1.(6)
 EXHAUST FAN # 1 MUST BE 10 FT. FROM STARS. PAGE M1.01
 3- PLEASE REFER TO SECTION 1019.1.2 2004 FBC
 PENETRATIONS ( DUCT PENETRATING STAIR WELL ) PAGE M1.02
 .
 4- PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION
 SYSTEM AND SECTION 606.4.1 SUPERVISON 2004 FBC (M) PLAN
 REVIEW BY HAROLD MOSER 561-805-6732