Plan Review Notes For Permit 07090034 |
Permit Number |
07090034 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-29 11:20:00 | PLAN DENIED | | 1- PLEASE REFER TO SECTION 502.7.3.6 TERMINATION POINT | | # 2 (OUT DOOR AIR AND CONDENSORS ) PAGE M1.01. | | 2- PLEASE REFER TONFPA 101 SECTION 7.1.3.2.1.(6) | | EXHAUST FAN # 1 MUST BE 10 FT. FROM STARS. PAGE M1.01 | | 3- PLEASE REFER TO SECTION 1019.1.2 2004 FBC | | PENETRATIONS ( DUCT PENETRATING STAIR WELL ) PAGE M1.02 | | . | | 4- PLEASE REFER TO SECTION 606.2.1 SMOKE DETECTION | | SYSTEM AND SECTION 606.4.1 SUPERVISON 2004 FBC (M) PLAN | | REVIEW BY HAROLD MOSER 561-805-6732 |
|