2007-10-22 14:47:42 | 1. DUCTWORK APPEARS TO PASS THROUGH STAIR # 1 ON PAGE |
| M1.02. PLEASE PROVIDE DETAILS, MECHANICAL EQUIPMENT IS |
| NOT ALLOWED TO PASS THROUGH A REQUIRED EXIT STAIR. |
| |
| 2. FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE |
| FUTURE SPACES ARE LEASED. |
| |
| 3. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A |
| MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1" |
| WIDE SHALL BE PROVIDED. NUMBERS SHOULD CONTRAST WITH |
| THE BACKGROUND THEY ARE MOUNTED ON. |
| |
| 4. WHAT PROTECTION IS BEING AFFORDED TO EXITING FROM |
| STAIR # 1 AND TO EXITING OCCURING FROM THE EXTERIOR |
| STAIRS. IT APPEARS THAT DOORS IN THE LOBBY ARE NOT FIRE |
| RATED AND WINDOWS APPEAR TO BE WITHIN CLOSE PROXIMITY |
| TO THE EXTERIOR STAIR. THERE APPEARS TO BE NO |
| PROTECTION TO PROVIDE FOR EXITING. |
| |
| 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL HANDRAILS AND GUARDRAILS. |
| |
| 6. WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE |
| EXTERIOR FIRE STAIR. |
| |
| 7. ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR |
| OPENINGS. |
| |
| 8. ELEVATOR INSTALLATION TO COMPLY WITH ANSI A17.1. |
| |
| 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| |
| 10. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| WITH NFPA 241. |
| |
| 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| |
| 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| WALLS AND CEILINGS. |
| |
| 13. PLEASE ILLUSTRATE PORTABLE FIRE EXTINGUISHER |
| LOCATIONS. |
| |
| |