2007-10-22 14:47:421. DUCTWORK APPEARS TO PASS THROUGH STAIR # 1 ON PAGE
 M1.02. PLEASE PROVIDE DETAILS, MECHANICAL EQUIPMENT IS
 NOT ALLOWED TO PASS THROUGH A REQUIRED EXIT STAIR.
  
 2. FUTURE TENANT SEPARATIONS WILL BE REQUIRED WHEN THE
 FUTURE SPACES ARE LEASED.
  
 3. BUILDING ADDRESS REQUIRED ON PROPER ELEVATION. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1"
 WIDE SHALL BE PROVIDED. NUMBERS SHOULD CONTRAST WITH
 THE BACKGROUND THEY ARE MOUNTED ON.
  
 4. WHAT PROTECTION IS BEING AFFORDED TO EXITING FROM
 STAIR # 1 AND TO EXITING OCCURING FROM THE EXTERIOR
 STAIRS. IT APPEARS THAT DOORS IN THE LOBBY ARE NOT FIRE
 RATED AND WINDOWS APPEAR TO BE WITHIN CLOSE PROXIMITY
 TO THE EXTERIOR STAIR. THERE APPEARS TO BE NO
 PROTECTION TO PROVIDE FOR EXITING.
  
 5. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 6. WHAT SLIP RESISTANT METHODS ARE PLANNED FOR THE
 EXTERIOR FIRE STAIR.
  
 7. ELEVATOR WARNING SIGNS REQUIRED AT ELEVATOR
 OPENINGS.
  
 8. ELEVATOR INSTALLATION TO COMPLY WITH ANSI A17.1.
  
 9. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 10. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 11. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 12. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 13. PLEASE ILLUSTRATE PORTABLE FIRE EXTINGUISHER
 LOCATIONS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX