Date |
Text |
2007-10-07 14:15:30 | 2007-10-07 14:15:30 |
| |
| *** DENIED *** |
| |
| 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| NOT MADE BY OTHER TRADE(S). |
| |
| 2) NOTE: PLEASE SEE THE ADDRESS ON APPLICATION AND |
| ADDRESS IN OUR SYSTEM AS APPLIED FOR WITH THE PCN |
| PROVIDED IS FOR 314 10TH ST, HOWEVER THE PLANS/COVER |
| SHEET CLEARLY INDICATES *310* 10TH ST?? |
| PLEASE COORDINATE AND CORRECT. |
| FBC 106.1.2, 110.1.2 |
| |
| 3) NOTE: PLEASE SEE THE TITLE BLOCKS ON THE LANDSCAPE |
| SHEETS ARE MISSING REQUIRED INFORMATION PER FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES |
| 481.219. |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADES** |
| |
| 4) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8 |
| AND 7.9 NEEDS TO BE MET. |
| PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY |
| BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING. |
| FOR EXAMPLE STAIRS WHICH ONLY INDICATE A *D* FIXTURE |
| WHICH BY FIXTURE LEGEND DOES NOT CONTAIN ANY BATTERY |
| BACK UP?? |
| PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS |
| PATHS INCLUDING THAT TO THE EXIT DISCHARGE |
| AREAS/PATHS. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE PART OF |
| THE EXIT DISCHARGE WHICH DOES NOT CONTAIN BATTERY BACK |
| UP LIGHTING. |
| PLEASE SEE AREAS AS THESE ARE EXIT PATHS HOWEVER AS |
| THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF WAY OR SAFE |
| DISTANCE FROM THE BUILDING, EMERGENCY LIGHTING FIXTURES |
| WILL BE REQUIRED. |
| PLEASE SEE THE ELEVATOR EQUIPMENT ROOM WILL BE REQUIRED |
| TO HAVE A BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE |
| SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL ARE |
| LISTED. |
| PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR |
| ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE |
| MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO |
| GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC |
| 106.1.2, FAC 61G15-33.004 |
| NFPA-101 7.8, 7.9 |
| |
| 5) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH |
| EXIT SIGNSAND A LIGHTING FIXTURE WITH BATTERY BACK UP |
| WILL BE REQUIRED FOE LIFE SAFETY. |
| PLEASE SEE THE FUTURE BUILD OUT SPACES WHICH WILL |
| REQUIRE THESE. PLEASE ALSO SEE THAT LIGHTING CONTROL |
| FOR OCCUPANCY SENSOR TYPE DEVICE(S) WILL BE REQUIRED. |
| THIS WAS CONFIRMED WITH THE FIRE MARSHAL. |
| PLEASE SEE NFPA-101 7.8, 7.9, FBC CHAPTER 10. |
| |
| 6) NOTE: PLEASE KNOW AS ZONING CONTAINS MINIMUM |
| REQUIREMENTS FOR DOWNTOWN MASTER PLAN AREAS AND PARKING |
| LOT LIGHTING, THIS WILL AFFECT COMMENTS 6 AND 7 BELOW. |
| AS NO SITE LIGHTING IS YET SUBMITTED, NO REVIEW CAN BE |
| DONE. |
| ZONING DOES HAVE MINIMUM PHOTO-METRIC LEVELS ALSO. |
| PLEASE CONTACT AMY STELLY FOR SECTION OF THE ZONING |
| ORDINANCE. |
| |
| 7) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13 |
| IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS. |
| |
| A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING |
| ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON |
| AREAS. |
| PLEASE CLARIFY HOW THE STANDARD 3-WAY SWITCHES BEING |
| SHOWN ON PLANS WILL COMPLY AND WORK WITH THE SYSTEM. |
| ALSO SOME S-POLE SWITCHES WITH NO AUTOMATED CONTROL |
| PLEASE SEE THE OVER RIDES SHALL BE LOCATED SO THE |
| OCCUPANT WHEN ENTERING A SPACE CAN NOT ONLY CONTROL THE |
| LIGHTING IN AN OVER RIDE CIRCUMSTANCE BUT MUST ALSO SEE |
| THE LIGHTING IN WHICH IS BEING CONTROLLED. THERE IS |
| ONLY ONE EXCEPTION TO THE LIGHTING FOR REQUIRED VISUAL |
| CONTACT OF LIGHTS BEING CONTROLLED. |
| PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN NEED TO STATE |
| THE MAXIMUM TIMES. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| |
| B) PLEASE SEE EXTERIOR LIGHTING CONTROLS AS A STANDARD |
| TIME CLOCK IS NOT ALL THAT IS REQUIRED. |
| 13-415.1.ABC.1.4 |
| |
| |
| 8) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR |
| ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS |
| NEEDS TO BE MET. |
| **IMPORTANT** PLEASE BE SURE TO SEE MECHANICAL REVIEW |
| COMMENTS FOR POSSIBLE METHOD BEING SUBMITTED AND USED |
| FOR WHAT IS BEING SHOWN AS SHELL ON PLANS.(ONLY NOTED) |
| PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO |
| THE INPUT DATA REPORT AS IDR. |
| |
| A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND |
| CONSUMES ENERGY WITH THAT OF THE IDR. |
| FOR EXAMPLE: |
| PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A |
| *NONE ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE |
| WHEN PLANS CLEARLY SHOW EXTERIOR LIGHTING? |
| |
| PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE |
| LIGHTING IN THE IDR. |
| PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH |
| NEEDS TO COORDINATE WITH PLANS. |
| PLEASE SEE THE AREAS DO NOT MATCH. |
| PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH |
| AREA/ROOM DESIGNATION DOES NOT CORRELATE. |
| PLEASE SEE THE IDR DOES NOT CONTAIN ALL LIGHTING AS |
| SHOWN ON PLANS AND THE FIXTURE LEGEND |
| PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL |
| ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING |
| CONTROLS ARE AUTOMATED ETC. |
| |
| ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS |
| WITH THE IDR. |
| PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW |
| OF MANY ITEMS CAN NOT BE DONE. |
| |
| PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES. |
| PLEASE SEE 13-415.1.A, 13-415.2 ETC. |
| |
| ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL |
| LIGHTING CONTROLS AND CALCULATIONS REQUIRED. |
| |
| 9) NOTE: PLEASE SEE ALL THREE SETS OF ENERGY |
| CALCULATIONS SUBMITTED CONTAIN A RAISED SEAL OVER A |
| *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED PER FAC |
| 61G15-23.002 AND FS 471.025. |
| PLEASE KNOW THIS OFFICE HAS INFORMED THIS SAME DESIGNER |
| ON PREVIOUS PROJECTS AS THIS IS NOT PERMITTED. PLEASE |
| BE SURE TO ADDRESS THIS ISSUE AS THESE WILL BE LEFT |
| WITH NO OTHER CHOICE BUT TO FORWARD THESE TO THE STATE |
| BOARD OF ENGINEERS AND LEGAL COUNSEL. |
| ** PLEASE BE SURE THE OWNER AGENT IS SIGNED PER |
| 13-103.1.1.1 |
| |
| |
| 10) NOTE: PLEASE CLARIFY THE GROUNDING AS AN *EQUIPMENT |
| GROUNDING CONDUCTOR* IS BEING SHOWN ON THE LINE SIDE OF |
| THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED. |
| PLEASE SEE 250.24BA AND 250.6 AS THIS WILL CREATE |
| OBJECTIONABLE CURRENTS. |
| |
| 250.50 **PLEASE PLACE NOTE ON PLANS FOR FBC 2704 WHICH |
| REQUIRES METAL FRAMING MEMBERS TO BE BONDED. |
| |
| 11) NOTE: THIS IS ONLY NOTED FOR INFORMATION ONLY: |
| PLEASE KNOW IF THE BUILDING CONTAINS A FA PANEL OR IS |
| REQUIRED TO HAVE ONE INSTALLED PER BUILDING OR FIRE |
| MARSHAL REVIEW, PLEASE BE SURE TO SEE FBC 2004 |
| 11-4.28.1, .2 AND .3(4) AND STATE THE MINIMUM HORN, |
| STROBE LEVELS ON PLANS FOR ADA REQUIRED AREAS. DEVICES |
| ARE BEING SHOWN ON PLANS/LEGEND. PLEASE CORRELATE WITH |
| PLANS, AND FA SHEETS SUBMITTED. THIS IS NOTED FOR |
| INFORMATION ONLY!! |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| SETS. |
| FBC 106.3.5.1.2 |
| |
| 12) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST |
| MOTOR LOADS AT 125%. |
| PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN) |
| |
| 13) NOTE: PLEASE SEE FEEDER CONDUIT/CONDUCTORS FROM |
| 225AMP CIRCUIT BREAKER MAIN IS BEING SHOWN GOING |
| THROUGH THE LINE GUTTER WHICH IS NOT PERMITTED. MAY NOT |
| INSTALL UNPROTECTED AND PROTECTED CONDUCTORS IN THE |
| SAME GUTTER AS SHOWN. |
| PLEASE ADJUST RISER AND SEE 230.7 AS * OTHER CONDUCTORS |
| IN RACEWAY OR CABLE |
| CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE |
| INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE |
| CABLE. |
| ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE |
| SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS |
| ARE NOT PROVIDED WITH OVER-CURRENT PROTECTION WHERE |
| THEY RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST |
| OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE |
| DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF |
| CURRENT THAT COULD BE IMPOSED ON FEEDER OR |
| BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME |
| RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN |
| THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT |
| CONDUCTORS.* |
| |
| 14) NOTE: PLEASE SEE DISCONNECTS AS SHOWN FOR THE |
| CONDENSING UNITS DO NOT MEET 110.26. |
| PLEASE ADJUST. |
| |
| 15) NOTE: PLEASE LABEL AND IDENTIFY ALL MAINS AND |
| FUTURE MAINS. |
| 230.2E. |
| EXAMPLE: MAIN 1OF 4, 2 OF 4 ETC |
| |
| 16) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE |
| SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. |
| PLEASE SEE 408.4. (MAY BE NUMERICAL DESIGNATIONS) |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.1.2, 106.5, 106.1.2 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
2007-10-07 13:05:38 | 2007-10-07 13:05:08 |
| |
| IN ELECTRIC FOR REVIEW |