Plan Review Notes
Plan Review Notes For Permit 07090034
Permit Number 07090034
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-07 14:15:302007-10-07 14:15:30
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS ON APPLICATION AND
 ADDRESS IN OUR SYSTEM AS APPLIED FOR WITH THE PCN
 PROVIDED IS FOR 314 10TH ST, HOWEVER THE PLANS/COVER
 SHEET CLEARLY INDICATES *310* 10TH ST??
 PLEASE COORDINATE AND CORRECT.
 FBC 106.1.2, 110.1.2
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS ON THE LANDSCAPE
 SHEETS ARE MISSING REQUIRED INFORMATION PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.219.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES**
  
 4) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH BATTERY
 BACK UP TYPE OF LIGHTING FIXTURES ARE MISSING.
 FOR EXAMPLE STAIRS WHICH ONLY INDICATE A *D* FIXTURE
 WHICH BY FIXTURE LEGEND DOES NOT CONTAIN ANY BATTERY
 BACK UP??
 PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS
 PATHS INCLUDING THAT TO THE EXIT DISCHARGE
 AREAS/PATHS.
  
 FOR EXAMPLE:
 PLEASE SEE THE STAIR AREAS OUTSIDE WHICH ARE PART OF
 THE EXIT DISCHARGE WHICH DOES NOT CONTAIN BATTERY BACK
 UP LIGHTING.
 PLEASE SEE AREAS AS THESE ARE EXIT PATHS HOWEVER AS
 THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF WAY OR SAFE
 DISTANCE FROM THE BUILDING, EMERGENCY LIGHTING FIXTURES
 WILL BE REQUIRED.
 PLEASE SEE THE ELEVATOR EQUIPMENT ROOM WILL BE REQUIRED
 TO HAVE A BATTERY BACK UP FIXTURE OF SOME TYPE. PLEASE
 SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL ARE
 LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 106.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 5) NOTE: PLEASE SEE THERE ARE SOME LOCATIONS IN WHICH
 EXIT SIGNSAND A LIGHTING FIXTURE WITH BATTERY BACK UP
 WILL BE REQUIRED FOE LIFE SAFETY.
 PLEASE SEE THE FUTURE BUILD OUT SPACES WHICH WILL
 REQUIRE THESE. PLEASE ALSO SEE THAT LIGHTING CONTROL
 FOR OCCUPANCY SENSOR TYPE DEVICE(S) WILL BE REQUIRED.
 THIS WAS CONFIRMED WITH THE FIRE MARSHAL.
 PLEASE SEE NFPA-101 7.8, 7.9, FBC CHAPTER 10.
  
 6) NOTE: PLEASE KNOW AS ZONING CONTAINS MINIMUM
 REQUIREMENTS FOR DOWNTOWN MASTER PLAN AREAS AND PARKING
 LOT LIGHTING, THIS WILL AFFECT COMMENTS 6 AND 7 BELOW.
 AS NO SITE LIGHTING IS YET SUBMITTED, NO REVIEW CAN BE
 DONE.
 ZONING DOES HAVE MINIMUM PHOTO-METRIC LEVELS ALSO.
 PLEASE CONTACT AMY STELLY FOR SECTION OF THE ZONING
 ORDINANCE.
  
 7) NOTE: PLEASE SEE THAT COMPLIANCE WITH FBC CHAPTER 13
 IS NEEDED FOR ALL LIGHTING CONTROLS IN ALL AREAS.
  
 A) PLEASE PROVIDE INFORMATION/DESIGN/TIME SCHEDULING
 ETC ON HOW LIGHTING IS BEING CONTROLLED IN COMMON
 AREAS.
 PLEASE CLARIFY HOW THE STANDARD 3-WAY SWITCHES BEING
 SHOWN ON PLANS WILL COMPLY AND WORK WITH THE SYSTEM.
 ALSO SOME S-POLE SWITCHES WITH NO AUTOMATED CONTROL
 PLEASE SEE THE OVER RIDES SHALL BE LOCATED SO THE
 OCCUPANT WHEN ENTERING A SPACE CAN NOT ONLY CONTROL THE
 LIGHTING IN AN OVER RIDE CIRCUMSTANCE BUT MUST ALSO SEE
 THE LIGHTING IN WHICH IS BEING CONTROLLED. THERE IS
 ONLY ONE EXCEPTION TO THE LIGHTING FOR REQUIRED VISUAL
 CONTACT OF LIGHTS BEING CONTROLLED.
 PLEASE SEE THE OCCUPANCY DEVICES AS SHOWN NEED TO STATE
 THE MAXIMUM TIMES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE EXTERIOR LIGHTING CONTROLS AS A STANDARD
 TIME CLOCK IS NOT ALL THAT IS REQUIRED.
 13-415.1.ABC.1.4
  
  
 8) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 FOR
 ENERGY CALCULATIONS/LIGHTING PERFORMANCE CALCULATIONS
 NEEDS TO BE MET.
 **IMPORTANT** PLEASE BE SURE TO SEE MECHANICAL REVIEW
 COMMENTS FOR POSSIBLE METHOD BEING SUBMITTED AND USED
 FOR WHAT IS BEING SHOWN AS SHELL ON PLANS.(ONLY NOTED)
 PLEASE SEE THE FOLLOWING WHICH WILL HAVE REFERENCE TO
 THE INPUT DATA REPORT AS IDR.
  
 A) PLEASE CORRELATE ALL LIGHTING WHICH IS ON PLANS AND
 CONSUMES ENERGY WITH THAT OF THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING WHICH INDICATES A
 *NONE ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE
 WHEN PLANS CLEARLY SHOW EXTERIOR LIGHTING?
  
 PLEASE BE SURE THE FIXTURE LEGEND COORDINATES WITH THE
 LIGHTING IN THE IDR.
 PLEASE ALSO SEE FOR EXAMPLE THE INTERIOR LIGHTING WHICH
 NEEDS TO COORDINATE WITH PLANS.
 PLEASE SEE THE AREAS DO NOT MATCH.
 PLEASE SEE THE NUMBER OF FIXTURES ON EACH AND EACH
 AREA/ROOM DESIGNATION DOES NOT CORRELATE.
 PLEASE SEE THE IDR DOES NOT CONTAIN ALL LIGHTING AS
 SHOWN ON PLANS AND THE FIXTURE LEGEND
 PLEASE SEE THE METHOD OF CONTROLS INDICATES *MANUAL
 ON/OFF* WHICH IS ALSO NOT POSSIBLE WHEN LIGHTING
 CONTROLS ARE AUTOMATED ETC.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURES ON PLANS
 WITH THE IDR.
 PLEASE SEPARATE TO ROOMS AND AREAS ON THE IDR. REVIEW
 OF MANY ITEMS CAN NOT BE DONE.
  
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR ALLOWANCES.
 PLEASE SEE 13-415.1.A, 13-415.2 ETC.
  
 ** PLEASE SEE 2004 FBC CHAPTER 13 FOR ALL ELECTRICAL
 LIGHTING CONTROLS AND CALCULATIONS REQUIRED.
  
 9) NOTE: PLEASE SEE ALL THREE SETS OF ENERGY
 CALCULATIONS SUBMITTED CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED PER FAC
 61G15-23.002 AND FS 471.025.
 PLEASE KNOW THIS OFFICE HAS INFORMED THIS SAME DESIGNER
 ON PREVIOUS PROJECTS AS THIS IS NOT PERMITTED. PLEASE
 BE SURE TO ADDRESS THIS ISSUE AS THESE WILL BE LEFT
 WITH NO OTHER CHOICE BUT TO FORWARD THESE TO THE STATE
 BOARD OF ENGINEERS AND LEGAL COUNSEL.
 ** PLEASE BE SURE THE OWNER AGENT IS SIGNED PER
 13-103.1.1.1
  
  
 10) NOTE: PLEASE CLARIFY THE GROUNDING AS AN *EQUIPMENT
 GROUNDING CONDUCTOR* IS BEING SHOWN ON THE LINE SIDE OF
 THE FIRST MEANS OF DISCONNECT WHICH IS NOT PERMITTED.
 PLEASE SEE 250.24BA AND 250.6 AS THIS WILL CREATE
 OBJECTIONABLE CURRENTS.
  
 250.50 **PLEASE PLACE NOTE ON PLANS FOR FBC 2704 WHICH
 REQUIRES METAL FRAMING MEMBERS TO BE BONDED.
  
 11) NOTE: THIS IS ONLY NOTED FOR INFORMATION ONLY:
 PLEASE KNOW IF THE BUILDING CONTAINS A FA PANEL OR IS
 REQUIRED TO HAVE ONE INSTALLED PER BUILDING OR FIRE
 MARSHAL REVIEW, PLEASE BE SURE TO SEE FBC 2004
 11-4.28.1, .2 AND .3(4) AND STATE THE MINIMUM HORN,
 STROBE LEVELS ON PLANS FOR ADA REQUIRED AREAS. DEVICES
 ARE BEING SHOWN ON PLANS/LEGEND. PLEASE CORRELATE WITH
 PLANS, AND FA SHEETS SUBMITTED. THIS IS NOTED FOR
 INFORMATION ONLY!!
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE CLARIFY ALL CONTINUOUS AND LARGEST
 MOTOR LOADS AT 125%.
 PLEASE SHOW. 215.3, 230.42 (SOME ARE SHOWN)
  
 13) NOTE: PLEASE SEE FEEDER CONDUIT/CONDUCTORS FROM
 225AMP CIRCUIT BREAKER MAIN IS BEING SHOWN GOING
 THROUGH THE LINE GUTTER WHICH IS NOT PERMITTED. MAY NOT
 INSTALL UNPROTECTED AND PROTECTED CONDUCTORS IN THE
 SAME GUTTER AS SHOWN.
 PLEASE ADJUST RISER AND SEE 230.7 AS * OTHER CONDUCTORS
 IN RACEWAY OR CABLE
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE
 CABLE.
 ALL FEEDER AND BRANCH-CIRCUIT CONDUCTORS MUST BE
 SEPARATED FROM SERVICE CONDUCTORS. SERVICE CONDUCTORS
 ARE NOT PROVIDED WITH OVER-CURRENT PROTECTION WHERE
 THEY RECEIVE THEIR SUPPLY; THEY ARE PROTECTED AGAINST
 OVERLOAD CONDITIONS AT THEIR LOAD END BY THE SERVICE
 DISCONNECT FUSES OR CIRCUIT BREAKERS. THE AMOUNT OF
 CURRENT THAT COULD BE IMPOSED ON FEEDER OR
 BRANCH-CIRCUIT CONDUCTORS, SHOULD THEY BE IN THE SAME
 RACEWAY AND A FAULT OCCUR, WOULD BE MUCH HIGHER THAN
 THE AMPACITY OF THE FEEDER OR BRANCH-CIRCUIT
 CONDUCTORS.*
  
 14) NOTE: PLEASE SEE DISCONNECTS AS SHOWN FOR THE
 CONDENSING UNITS DO NOT MEET 110.26.
 PLEASE ADJUST.
  
 15) NOTE: PLEASE LABEL AND IDENTIFY ALL MAINS AND
 FUTURE MAINS.
 230.2E.
 EXAMPLE: MAIN 1OF 4, 2 OF 4 ETC
  
 16) NOTE: PLEASE SEE THAT PANEL SCHEDULES ARE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE 408.4. (MAY BE NUMERICAL DESIGNATIONS)
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2, 106.5, 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-10-07 13:05:382007-10-07 13:05:08
  
 IN ELECTRIC FOR REVIEW