2007-10-15 17:05:09 | BUILDING PLAN REVIEW |
| PERMIT: 07090034 |
| ADD: 314 10TH ST |
| CONT: KENNEDY CONTRACTORS, INC |
| TEL: (561)434-1300 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. |
| IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE2007 REVISIONS. |
| |
| 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| OF OCCUPANCY: |
| A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT |
| IS DESIGNED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED INTABLE 503 |
| & TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED |
| F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| .H ) SQ. FT. FOOTPRINT |
| |
| 3) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 4) SP-1 PLEASE PROVIDE ADDITIONAL INFORMATION AS HOW |
| THE ACCESSIBLE ROUTE FROM THE HANDICAPPED PARKING SPACE |
| AT ELEVATION 13.5?TO THE FINISH FLOOR ELEVATION OF |
| 14.0?. |
| 11-4.3.2(3). SHEET S-1 DETAIL# 7 IS NOT CLEAR IF THERE |
| IS A |
| |
| 5) AREAS OF RESCUE ASSISTANCE ARE REQUIRED IN 2 STORY |
| BUILDINGS NOT HAVING FIRE SPRINKLERS, PLEASE SEE |
| 11-4.1.3 EXCEPTION# 9. |
| IN BUILDINGS OR FACILITIES, OR PORTIONS OF |
| BUILDINGS OR FACILITIES, REQUIRED TO BE ACCESSIBLE, |
| ACCESSIBLE MEANS OF EGRESS SHALL BE PROVIDED IN THE |
| SAME NUMBER AS REQUIRED FOR EXITS BY LOCAL |
| BUILDING/LIFE SAFETY REGULATIONS. WHERE A REQUIRED EXIT |
| FROM AN OCCUPIABLE LEVEL ABOVE OR BELOW A LEVEL OF |
| ACCESSIBLE EXIT DISCHARGE IS NOT ACCESSIBLE, AN AREA OF |
| RESCUE ASSISTANCE SHALL BE PROVIDED ON EACH SUCH LEVEL |
| (IN A NUMBER EQUAL TO THAT OF INACCESSIBLE REQUIRED |
| EXITS).AREAS OF RESCUE ASSISTANCE SHALL COMPLY WITH |
| SECTION 11-4.3.11 . A HORIZONTAL EXIT, MEETING THE |
| REQUIREMENTS OF LOCAL BUILDING/LIFE SAFETY REGULATIONS, |
| SHALL SATISFY THE REQUIREMENT FOR AN AREA OF RESCUE |
| ASSISTANCE. |
| EXCEPTION: AREAS OF RESCUE ASSISTANCE ARE NOT REQUIRED |
| IN BUILDINGS OR FACILITIES HAVING A SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM. |
| |
| 6) SHEET A-01 PLANS INDICATE A SECOND FLOOR, THERE IS |
| NO MENTION OF THE USE OF FIRE SPRINKLERS FOR THIS |
| BUILDING. PLEASE SEE 11-4.3.11 (1-5) THESE REQUIREMENTS |
| ARE TO BE MET FORAREAS OF RESCUE ASSISTANCE, PLEASE |
| PROVIDE INFORMATION FOR COMPLIANCE WITH THESE SECTIONS. |
| |
| |
| 7) SHEET A-01 & A-04 INDICATE STAIRWELL# 1, THE DETAILS |
| DO NOT PROVIDE INFORMATION FOR BARRIERS TO WARN |
| VISUALLY IMPAIRED PERSONS SEE 11-4.4.2 & FIGURE 8-C1. |
| THE EXTERIOR STAIRS WILL NEED THE SAME BARRIER FOR THE |
| VISUALLY IMPAIRED. |
| |
| 8) SHEET A-04 STAIR# 1 SECTION OF GUARDRAIL/ HANDRAIL |
| .THIS IS AN OFFICE OCCUPANCY THAT WILL NEED TO HAVE THE |
| GUARDRAIL CONFORM TO SECTION 1012.3. 4? CENTERS. |
| |
| 9) SHEET A-04 DETAIL# 3 IS FOR A 1-HR RATED WALL, |
| PLEASE PROVIDE THE UL NUMBER OR GYPSUM |
| ASSOCIATION LISTING NUMBER FOR A 1 HOUR RATED ASSEMBLY. |
| 707.4. |
| |
| 10)SHEET A-01 THE FIRST FLOOR LOBBY WILL REQUIRE A |
| 1-HR RATING. THIS BUILDING DOES NOT INDICATE THE USE OF |
| FIRE SPRINKLERS, PLEASE SEE TABLE 1016.1 BUSINESS |
| OCCUPANCY CORRIDORS SERVING A OCCUPANT LOAD GREATER |
| THAN 30 WILL REQUIRE A 1 HR RATING. |
| |
| 11) SHEET A-01 THERE IS NO WALL TAGS IDENTIFYING THE |
| TYPE OF WALL CONFIGURATION TO BE USED. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. ELEVATOR PUMP |
| ROOM, ELEVATOR, STAIRWELL, LOBBY AND OR TENANT |
| SEPARATION WALLS. |
| |
| 12) SHEET A-4 STAIRWELL NUMBER 1 DOES NOT PROVIDE A CUT |
| SECTION THROUGH THE CEILING PROVIDING WHAT TYPE OF |
| MATERIAL AND OR RATING WILL BE APPLIED TO THE CEILING |
| OF THE STAIRWELL. ADDITIONAL INFORMATION REQUIRED, |
| 106.1.2. |
| |
| 13) SHEET A-01 DOOR NUMBER 6 & 7 WILL REQUIRE FIRE |
| RATED DOORS, PLEASE SEE 715.3 FOR OPENING |
| PROTECTIVE?S. |
| |
| 14)SHEET A-01 & A-03 INDICATE THE USE OF EXTERIOR |
| STAIRS. PLEASE SEE 1022.6 FOR REQUIRED SEPARATION FROM |
| THE INTERIOR OF THE BUILDING AS REQUIRED IN 1019.1, |
| ALSO SEE ATTACHED FIGURE 1022.6(1) FROM THE 2004 FBC |
| CODE COMMENTARY. |
| |
| 15) SHEET A-01 & A-03 STAIR # 2 DOES NOT PROVIDE THE |
| RISERNOR TREAD DIMENSION, SEE 1009.3. |
| |
| 16) STAIR# 2 DOES NOT PROVIDE INFORMATION ON THE |
| HANDRAIL OR GUARDRAIL FOR THIS EXTERIOR STAIR, NOTED |
| THIS IS A PRE-FAB ENGINEERED STEEL STAIR, AGAIN THERE |
| IS NO INFORMATION FOR ATTACHMENT OF STAIRS TO |
| STRUCTURE. ADDITIONAL INFORMATION REQUIRED. 106.1.2. |
| |
| 17)SHEET A-01 ON THE 2ND FLOOR THE PLANS INDICATE THE |
| USE OF A BREAK ROOM SINK, THE PLANS DO NOT PROVIDE AN |
| ELEVATION OF THIS AREA PLEASE COMPLY WITH THE |
| FOLLOWING: |
| SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED |
| WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH |
| FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 18) PLANS DO NOT PROVIDE ANY INFORMATION ON |
| PENETRATIONS OF HORIZONTAL ASSEMBLIES, |
| 711.5 PENETRATIONS .PENETRATIONS THROUGH |
| FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL |
| COMPLY WITH SECTION 712 . 712.4.1.1 |
| FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN |
| APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. |
| PLEASE PROVIDE DETAILS FOR PENETRATIONS THROUGH THE |
| FLOOR/ CEILING ASSEMBLY. |
| |
| |
| |
| 19)ENERGY CALCULATIONS SUBMITTED ARE FORM ?A? WHOLE |
| BUILDING METHOD WHERE AS THE FIRST FLOOR IS ONLY |
| ASSUMPTIONS AT THIS TIME, THE CORRECT FORM WOULD BE |
| EITHER ?B? OR ?C?. |
| 13-400.0A. NOTE NO INSULATION IS INDICATED ON THE FIRST |
| FLOOR EXTERIOR WALLS, THE WHOLE BUILDING APPROACH , |
| METHOD ?A? CAN NOT BE USED. |
| |
| 20) THE SEALED SIGNATURE ON THE ENERGY CALCULATION IS |
| EITHER A STAMP OR COPY OF THE ORIGINAL SIGNATURE. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| PROFESSIONAL AFFIXED TO THE DOCUMENT. FL STATE STAT: |
| 61G15-23.002 ENGINEERS |
| |
| 21) ENERGY CALCULATIONS, SYSTEMS SUMMARY REPORT, PLEASE |
| RECHECK THE AMOUNT OF WINDOW OPENING IN EACH ZONE AND |
| WALL FACE, AS WELL AS DOORS. THE EXTERIOR DOORS WERE |
| NOT EVEN FILLED IN! 106.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 22)PLANS FAIL TO INDICATE COMPLIANCE WITH 1209.2 |
| ATTIC ACCESS, PLEASE PROVIDE WHERE THE ATTIC ACCESS |
| SHALL BE. |
| |
| 23) SHEET A-04 DETAIL NUMBER 4 PROVIDES A EXTERIOR WALL |
| AND ROOF SECTION. THE PLANS NEED TO SHOW COMPLIANCE |
| WITH : 1203.250 PERCENT OF THE REQUIRED VENTILATING |
| AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER |
| PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET |
| (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE |
| OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE |
| VENTS. |
| |
| 24)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) SINGLE HUNG WINDOWS |
| B) FIXED/ STOREFRONT WINDOWS |
| C) MULLIONS VERTICAL |
| D) SIDE LITES |
| E) SWING GLAZED DOORS |
| F) EXTERIOR HOLLOW METAL SWING DOORS |
| G) TRUSS ANCHORS |
| H) ROOF ASSEMBLIES |
| |
| 25)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. |
| 26) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 27) SHEET S-2 ROOF FRAMING PLAN IS MISSING THE DORMER |
| SECTION OF THE ROOF, PLEASE PROVIDE |
| A SECTION INDICATING HOW THE FRONT, SIDE WALLS WILL TIE |
| INTO THE MAIN ROOFING SYSTEM. |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 28) SHEET S-2 ROOF FRAMING PLAN AND NOTES INDICATE THE |
| UPLIFT LOAD CALCS ARE LOCATED ON SHEET S-4, WHERE? |
| ADDITIONAL INFORMATION REQUIRED 106.1.2. |
| |
| 29)SHEET S-2ND FLOOR DETAIL# 11 INDICATES A METAL |
| DECK AND CONCRETE BUT NO INFORMATION AS TO THE TYPE OF |
| STEEL NOR STRENGTH AND TYPE OF THE CONCRETE MIX TO BE |
| USED FOR THIS SLAB. |
| NOTE S-3 FLOOR DECK NOTE# 4 INDICATES A MINIMUM YIELD |
| STRENGTH OF 33,000PSI? |
| |
| 30)NOTE PLANS DO NOT INDICATE ANY WINDOW BUCK |
| ATTACHMENT TO THE STRUCTURE. |
| 1714.5.4.1 ANCHORING REQUIREMENTS. |
| WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN |
| ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S |
| RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE |
| SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR |
| SUBSTRATES NOT SPECIFIED BY THE FENESTRATION |
| MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING |
| PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING |
| PRACTICE. |
| |
| 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL |
| SUBSTRATE. |
| WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1? |
| INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE |
| ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR |
| SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S |
| PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE |
| SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE |
| OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS |
| OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE |
| ROUGH OPENING SUBSTRATE. |
| |
| 31)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |