2007-10-01 15:08:59 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)SEE ZONING COMMENTS REGARDING ACCESSIBLE PARKING. |
| |
| 2.)SEE ZONING COMMENTS REGARDING CONVEYANCE OF CITY |
| PROPERTY.THIS IS NOT REFLECTED ON THE SITE PLAN. |
| DOES THE SITE PLAN SHOW ALL CURRENT PROPERTY LINES? |
| WILL UNITY OF TITLE BE REQUIRED? |
| |
| 3.)DECLARE THE TOTAL NUMBER OF PARKINGS SPACES |
| INCLUDING NEW SPACES, TOTAL NUMBER OF ACCESSIBLE |
| SPACES, FBC11-4.1.295)(A). |
| |
| 4.)PROVIDE A COMPLETE SITE PLAN SHOWING BUILDING |
| LOCATION AND ALL ACCESSIBLE PARKING SPACES, |
| FBC11-4.6.2. |
| |
| 5.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. |
| |
| 6.)DECLARE GOVERNING CODE.INCLUDE 2007 AMENDMENTS |
| IN THE GOVERNING CODE. |
| |
| 6.)PROVIDE PRODUCT APPROVALS FOR THE MODIFIED |
| BITUMEN.PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| DESIGNER OF RECORD FBC*106 |
| |
| 7.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. |
| |
| 8.)IT APPEARS THAT THE ELEVATED DECK WILL BE |
| APPROXIMATELY 7' ABOVE GRADE.GUARD(RAIL)S REQUIRED, |
| FBC1012.1.THE PLANTERS SHOWN ARE NOT CONTINUOUS AND |
| DO NOT MEET THE HEIGHT REQUIREMENT. |
| |