Plan Review Notes
Plan Review Notes For Permit 07080943
Permit Number 07080943
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-16 11:56:10**** PROVISO/REVISION NEEDED****
  
  
 1) NOTE:PLANS MISSING LIGHTING POWER DENSITIES FOR
 NEW OFFICES PER 13-415.2
  
 2) NOTE: PLANS MISSING MAXIMUM TIMES FOR OS DEVICES PER
 13-415.1.ABC.1.1(MAX 30MINS)
  
 3) NOTE: PLANS STILL INDICATE THE TELCO ROOM AS
 EXISTING ALONG WITH AN IT PANEL IN WHICH THIS OFFICE
 HAS NO RECORD OF THIS WORK BEING PERMITTED IN OUR
 CURRENT SYSTEM GOING BACK ALMOST 10YEARS.
 THE CONTRACTOR HAS NOW VOIDED PREVIOUS APPLIED FOR
 PERMIT FOR IT ROOM EXPANSION. (# 06101010)
 THE ENGINEER OF RECORD KNOWS OF PREVIOUS WORK APPLIED
 FOR UNDER #06101010.
 THE SERVICE AND WORK SHOWN AS *EXISTING* SHALL BE
 VERIFIED IN FIELD BY INSPECTION SERVICES STAFF. ALL
 INFORMATION WAS FORWARDED TO BOTH ASSISTANT BUILDING
 OFFICIALS TO BE ADDRESSED.
  
 4) NOTE: PLEASE REVISE PLANS AS NEEDED FOR NOTES #1 AND
 2 BEFORE ROUGH ELECTRICAL INSPECTION UNDER THE
 PERMITTED SCOPE OF WORK.
 ANY CORRECTION NOTICES ISSUED IN FIELD FOR OTHER SCOPE
 OF WORK WILL BE ADDRESSED AT THAT TIME.
 ** IF PLANS COME BACK FOR CORRECTIONS FROM ANY OTHER
 TRADES, PLEASE ADDRESS AT THAT TIME, THIS WILL
 ALLEVIATE THE NEED FOR A REVISION AT A LATER DATE
 BEFORE ROUGH.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]