2007-10-16 11:56:10 | **** PROVISO/REVISION NEEDED**** |
| |
| |
| 1) NOTE:PLANS MISSING LIGHTING POWER DENSITIES FOR |
| NEW OFFICES PER 13-415.2 |
| |
| 2) NOTE: PLANS MISSING MAXIMUM TIMES FOR OS DEVICES PER |
| 13-415.1.ABC.1.1(MAX 30MINS) |
| |
| 3) NOTE: PLANS STILL INDICATE THE TELCO ROOM AS |
| EXISTING ALONG WITH AN IT PANEL IN WHICH THIS OFFICE |
| HAS NO RECORD OF THIS WORK BEING PERMITTED IN OUR |
| CURRENT SYSTEM GOING BACK ALMOST 10YEARS. |
| THE CONTRACTOR HAS NOW VOIDED PREVIOUS APPLIED FOR |
| PERMIT FOR IT ROOM EXPANSION. (# 06101010) |
| THE ENGINEER OF RECORD KNOWS OF PREVIOUS WORK APPLIED |
| FOR UNDER #06101010. |
| THE SERVICE AND WORK SHOWN AS *EXISTING* SHALL BE |
| VERIFIED IN FIELD BY INSPECTION SERVICES STAFF. ALL |
| INFORMATION WAS FORWARDED TO BOTH ASSISTANT BUILDING |
| OFFICIALS TO BE ADDRESSED. |
| |
| 4) NOTE: PLEASE REVISE PLANS AS NEEDED FOR NOTES #1 AND |
| 2 BEFORE ROUGH ELECTRICAL INSPECTION UNDER THE |
| PERMITTED SCOPE OF WORK. |
| ANY CORRECTION NOTICES ISSUED IN FIELD FOR OTHER SCOPE |
| OF WORK WILL BE ADDRESSED AT THAT TIME. |
| ** IF PLANS COME BACK FOR CORRECTIONS FROM ANY OTHER |
| TRADES, PLEASE ADDRESS AT THAT TIME, THIS WILL |
| ALLEVIATE THE NEED FOR A REVISION AT A LATER DATE |
| BEFORE ROUGH. |
| |