2007-09-13 10:21:15 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING WITH 2006 REVISIONS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. MORE INFORMATION IS REQUIRED FOR THE MAIN BATHROOM |
| AND KITCHEN WORK PER FBC-2004 CHAPTER 1, SECTION |
| 106.1.1. |
| |
| A} IF PLUMBING LAYOUT IS THE SAME |
| WITH NO CHANGES, PLEASE INDICATE THIS ON |
| THE DRAWING. |
| |
| B} IF PLUMBING LAYOUT IS THE |
| SAME AND THE PLUMBING FIXTURES ARE TO BE |
| CHANGED, PLEASE INDCATE ON THE DRAWING. |
| "EXACT FIXTURE CHANGE OUT ONLY" AND CLEARLY INDICATE |
| WHAT FIXTURES ARE BEING REPLACED ON THE RESUBMITTED |
| DRAWINGS. |
| |
| C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT |
| FROM THE EXISTING PLEASE INDICATE ON SEPERATE FLOOR |
| PLAN DRAWINGS THE EXISTING FLOOR PLAN LAYOUT AND THE |
| NEW PROPOSED BATHROOM AND KITCHEN LAYOUT AND FOLLOW |
| WHAT IS REQUIRED IN COMMENT #2. |
| |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| LOCATIONS. |
| |
| 3. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL |
| DOCUMENTS. CONSTRUCTION |
| DOCUMENTS, SPECIAL INSPECTION AND |
| STRUCTURAL OBSERVATION PROGRAMS, AND |
| OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| MORE SETS WITH EACH APPLICATION FOR A |
| PERMIT. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |