Plan Review Notes
Plan Review Notes For Permit 07080940
Permit Number 07080940
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-13 10:21:15DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED FOR THE MAIN BATHROOM
 AND KITCHEN WORK PER FBC-2004 CHAPTER 1, SECTION
 106.1.1.
  
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
  
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY" AND CLEARLY INDICATE
 WHAT FIXTURES ARE BEING REPLACED ON THE RESUBMITTED
 DRAWINGS.
  
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE INDICATE ON SEPERATE FLOOR
 PLAN DRAWINGS THE EXISTING FLOOR PLAN LAYOUT AND THE
 NEW PROPOSED BATHROOM AND KITCHEN LAYOUT AND FOLLOW
 WHAT IS REQUIRED IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  