Plan Review Notes
Plan Review Notes For Permit 07080940
Permit Number 07080940
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-11 07:16:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE FBC*106.3.5.4, MINIMUM PLAN REVIEW CRITERIA
 FOR RESIDENTIAL BUIDLINGS.NO PLANS PROVIDED WITH
 APPLICATION.
  
 2.)TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT
 ISSUANCE.
  
 3.)ROOFING IS NOT WITHIN THE SCOPE OF A GENERAL
 CONTRACTOR LICENSE.SEPARATE PERMIT WILL BE REQUIRED.
  
 4.)PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF ALL
 WORK TO BE COVERED UNDER THIS PERMIT.
  
 5.)PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.SHOW COMPLIANCE WITH
 EMERGENCY EGRESS REQUIREMENTS FOR BEDROOMS.
  
 6.)SEE ATTACHED INSTALLATION SCHEDULE; REQUIRED FOR
 HURRICANE SHUTTERS.PLEASE COMPLETE THE FORM AND SHOW
 PANEL LOCATIONS ON A FLOOR PLAN WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FOR ALL COMPONENTS AND CLADDING (ROOF, HURRICANE
 PANELS, WINDOWS).FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 8.)PROVIDE A DETAIL FOR THE WALL REPAIR AND STRAPPING
 IN THE LAUNDRY ROOM.
  
 9.)PLANS SHOULD STATE GOVERNING CODE AND WIND DESIGN
 CIRTERIA FBC1603.1.4.
  
 10.)FOR THE FLAT ROOF, INDICATE WHICH APPROVED
 ASSEMBLY AND FASTENER YOU ARE USING.
  
 11.) FOR THE FLAT DECK, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.