2007-09-11 07:16:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| FBC2004 |
| FACFLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)SEE FBC*106.3.5.4, MINIMUM PLAN REVIEW CRITERIA |
| FOR RESIDENTIAL BUIDLINGS.NO PLANS PROVIDED WITH |
| APPLICATION. |
| |
| 2.)TWO COMPLETE COLLATED SETS REQUIRED FOR PERMIT |
| ISSUANCE. |
| |
| 3.)ROOFING IS NOT WITHIN THE SCOPE OF A GENERAL |
| CONTRACTOR LICENSE.SEPARATE PERMIT WILL BE REQUIRED. |
| |
| 4.)PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF ALL |
| WORK TO BE COVERED UNDER THIS PERMIT. |
| |
| 5.)PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING |
| CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| BEDROOMS, FBC R310, FBC EB 505.1.SHOW COMPLIANCE WITH |
| EMERGENCY EGRESS REQUIREMENTS FOR BEDROOMS. |
| |
| 6.)SEE ATTACHED INSTALLATION SCHEDULE; REQUIRED FOR |
| HURRICANE SHUTTERS.PLEASE COMPLETE THE FORM AND SHOW |
| PANEL LOCATIONS ON A FLOOR PLAN WHICH CORRELATES WITH |
| THE INSTALLATION SCHEDULE. |
| |
| 7.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| FOR ALL COMPONENTS AND CLADDING (ROOF, HURRICANE |
| PANELS, WINDOWS).FAC9B72, WWW.FLORIDABUILDING.ORG. |
| |
| 8.)PROVIDE A DETAIL FOR THE WALL REPAIR AND STRAPPING |
| IN THE LAUNDRY ROOM. |
| |
| 9.)PLANS SHOULD STATE GOVERNING CODE AND WIND DESIGN |
| CIRTERIA FBC1603.1.4. |
| |
| 10.)FOR THE FLAT ROOF, INDICATE WHICH APPROVED |
| ASSEMBLY AND FASTENER YOU ARE USING. |
| |
| 11.) FOR THE FLAT DECK, SPECIFY THE ENHANCED FASTENING |
| FOR CORNER AND PERIMETER ZONES. |