2007-11-02 08:40:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. THE ADDRESS SHALL INCLUDE THE UNIT/SUITE NUMBER AND
 SHALL BE INDICATED ON THE APPLICATION AND THE TITLE
 BLOCK OF EACH SHEET. SECTION 106.1.1.
  
 2. SHT P3.1 INDICATES THE WATER SUPPLY TO CONNECT
 BETWEEN THE METER AND THE BACKFLOW PREVENTOR. EACH UNIT
 SHOULD BE SEPARATELY METERED AND BY METERING ALL WATER
 FOR BOTH SPACES THROUGH THE EXISTING METER THERE MAY BE
 A CONFLICT WHERE THE RESTAURANT SPACE COULD BE CHARGED
 FOR THE WATER FOR BOTH SPACES. THE MERCANTILE SPACE
 COULD THEN POSSIBLY BE CHARGED AGAIN FOR ITS WATER USE.
 THE WATER CONNECTION SHOULD MADE UPSTREAM OF THE METER
 FOR THE RESTAURANT SPACE. MUNICIPAL CODE ARTICLE III
 SECTION 90-31(E).
  
 3. A SEPARATE RPZV BACKFLOW MAY BE REQUIRED FOR THE NEW
 MERCANTILE UNIT. SECTION 608.13.2.
  