Plan Review Notes
Plan Review Notes For Permit 07080934
Permit Number 07080934
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-23 10:30:582007-09-23 10:30:58
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE ADDRESS FOR UNIT/SUITE SHALL BE
 STATED ON PERMIT APPLICATION AND TITLE BLOCKS FOR
 PLANS.
 A COPY OF PERMIT APPLICATION WAS ROUTED TO ADDRESSING
 REVIEWER. PLEASE BE AWARE OF ANY DESIGNATIONS WHICH MAY
 BE ASSIGNED.
  
 3) NOTE: PLEASE CLARIFY THE PANEL HL, IS THIS A *HOUSE
 PANEL*? PLEASE ALSO BE SURE TO CONTACT CITY ENGINEERING
 DEPARTMENT FOR ANY LIGHTING WHICH ACTUALLY MAY BE
 LOCATED IN THE *RIGHT OF WAY*. THIS MAY NOT BE
 PERMITTED AND ONLY LIGHTING LOCATED ON THE LEGAL
 PROPERTY MAY BE FED FROM BUILDING ELECTRICAL SERVICE.
 RIGHT OF WAY LIGHTING IS TYPICALLY FED FROM THE CITY
 POWER LOCATED IN RIGHT OF WAYS.
  
 4) NOTE: PLEASE SEE THE LIGHTING IN THE NEW *FUTURE
 RETAIL* IS BEING SHOWN ON CIRCUITS TO PANEL *HB*> THIS
 IS A 277/480V PANEL FOR TRACK LIGHTING.
 PLEASE SEE PANEL *HB* DOES NOT CONTAIN ANY LIGHTING
 CIRCUITS AND THE CIRCUITS AS REFERENCED ARE INDICATING
 OTHER CIRCUITS.
 THIS APPEARS THAT THESE SHOULD HAVE BEEN TO PANEL
 *LB*??
 PLEASE ADJUST AND COORDINATE CIRCUITS WITH PANEL
 SCHEDULE.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE RISER INDICATES THE TRANSFORMER
 IN THE RETAIL SPACE AS *THB* ALONG WITH THE TRANSFORMER
 LEGEND HOWEVER PLEASE SEE PANEL *HB* AS THIS PANEL
 INDICATES A TRANSFORMER *T1B*.
 PLEASE CORRELATE AND ADJUST. PLEASE ALSO SEE NEXT
 COMMENT.
  
 6) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING
 SHOWN AS 45KVA UNIT IS BEING SHOWN WITH 110AMP OVER
 CURRENT PROTECTION IN PANEL *HB* WHICH IS NOT
 PERMITTED. PLEASE SEE 450.3 AS THE OCP IS TO BE A
 MAXIMUM OF 125%.(UNLESS MEETING EXCEPTION WHICH THIS
 TRANSFORMER DOES NOT INDICATE).
 PLEASE CORRELATE AND ADJUST.
 THIS COMMENT IS BEING *ASSUMED* AS THE TRANSFORMER AS
 LISTED ON PANEL *HB* DOES NOT HAVE THE SAME
 DESIGNATIONS AS SHOWN ON RISER AND TRANSFORMER LEGEND.
 FBC 106.1.2.
  
 7) NOTE: PLEASE CLARIFY WHERE CONTINUOUS LOADS ARE
 SHOWN.
 215.3, 230.42, 220 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE CLARIFY THE USE OF AN *E-MON* METER. IF
 THIS IS GOING TO BE A NEW RETAIL TENANT SPACE, WOULD
 NOT A METER FROM FPL BE INSTALLED?
 PLEASE KNOW THE PLANS WILL BE ROUTED TO ZONING FOR
 DIVISION OF SPACES AND TENANTS.
 PLEASE CONTACT THE FPL SERVICE REPRESENTATIVE. PLEASE
 BE SURE TO INDICATE ANY *FLOATING NEUTRAL* KITS WHICH
 ARE TO BE INSTALLED AFTER THE FIRST MEANS OF DISCONNECT
 PER 250.6, 250.24.
  
 9) NOTE: PLEASE SEE THAT LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW LIGHTING BEING ADDED TO EXISTING
 PER 13-415.2.ABC.1.2, 13-415.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-23 09:48:002007-09-23 09:48:00
  
 PLANS REMOVED FROM INCOMING WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW
 IS COMPLETED.