Plan Review Notes For Permit 07080884 |
Permit Number |
07080884 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-02-26 08:51:38 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 | | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH | | THE FOLLOWING: | | | | 1} THERE IS NO CONDENSER LOCATION FOR THE A/C SYSTEM | | BEING INSTALLED, LOCATE SAME ON THE PLAN. SHOW | | COMPLIANCE WITH 210.63 FOR THE RECEPTACLE, AND | | DISCONNECT PER 440.14. | | | | 2} THE PANEL SCHEDULE LISTS TWO "ACCU" #1 AND #2. THERE | | SHOULD BE AN AHU LISTED AND ONE ACCU (A/C CONDENSING | | UNIT). | | | | 3} THE SMALL APPLIANCE CIRCUITS REQUIRED BY 210.11(C) | | (1) ARE NOT LISTED ON THE PANEL SCHEDULE. | | | | 4} VERIFY THE SERVICE CONSISTS OF A "METER/ MAIN" | | COMBINATION, AND A MAIN LUG PANEL, OR A STANDARD METER | | WITH A MAIN BREAKER PANEL.215.5 NEC 106.1.3 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|