Plan Review Notes
Plan Review Notes For Permit 07080884
Permit Number 07080884
Review Stop E
Sequence Number 3
Notes
Date Text
2008-02-26 08:51:38 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} THERE IS NO CONDENSER LOCATION FOR THE A/C SYSTEM
 BEING INSTALLED, LOCATE SAME ON THE PLAN. SHOW
 COMPLIANCE WITH 210.63 FOR THE RECEPTACLE, AND
 DISCONNECT PER 440.14.
  
 2} THE PANEL SCHEDULE LISTS TWO "ACCU" #1 AND #2. THERE
 SHOULD BE AN AHU LISTED AND ONE ACCU (A/C CONDENSING
 UNIT).
  
 3} THE SMALL APPLIANCE CIRCUITS REQUIRED BY 210.11(C)
 (1) ARE NOT LISTED ON THE PANEL SCHEDULE.
  
 4} VERIFY THE SERVICE CONSISTS OF A "METER/ MAIN"
 COMBINATION, AND A MAIN LUG PANEL, OR A STANDARD METER
 WITH A MAIN BREAKER PANEL.215.5 NEC 106.1.3 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  