Plan Review Notes
Plan Review Notes For Permit 07080854
Permit Number 07080854
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-15 14:06:44DENIED;
 1. THE DESIGN PROFESSIONAL IS REQUIRED TO SIGN SEALED
 AND DATE THE PLANS SUBMITED. SEE FLORIDA STATUTES
 PARTII.
 2. STATE LICENSE NUMBER REQUIRED IN TITLE BLOCK.
 3.A} AUTOMATIC IRRIGATION CONTROLLER: THE CONTROLLER
 SHALL BE CAPABLE OF INCORPORATING A RAIN SHUT OFF
 DEVICE TO OVERRIDE THE IRRIGATION CYCLE WHEN ADEQUATE
 RAINFALL HAS OCCURED, AS REQUIRED BY FLORIDA STATUTES,
 SECTION 373.62.
 B} THE RAIN SWITCH SHALL BE PLACED ON A STATIONARY
 STRUCTURE MINIMUM OF 5-FOOT (1524MM) CLEARANCE FROM
 OTHER OUTDOOR EQUIPMENT, FREE AND CLEAR OF ANY TREE
 CANOPY OR OTHER OVERHEAD OBSTRUCTIONS, AND ABOVE THE
 HEIGHT OF THE SPRINKLER COVERAGE.
 PLUMBING PLAN REVIEW BY;