Plan Review Notes For Permit 07080854 |
Permit Number |
07080854 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-15 14:06:44 | DENIED; | | 1. THE DESIGN PROFESSIONAL IS REQUIRED TO SIGN SEALED | | AND DATE THE PLANS SUBMITED. SEE FLORIDA STATUTES | | PARTII. | | 2. STATE LICENSE NUMBER REQUIRED IN TITLE BLOCK. | | 3.A} AUTOMATIC IRRIGATION CONTROLLER: THE CONTROLLER | | SHALL BE CAPABLE OF INCORPORATING A RAIN SHUT OFF | | DEVICE TO OVERRIDE THE IRRIGATION CYCLE WHEN ADEQUATE | | RAINFALL HAS OCCURED, AS REQUIRED BY FLORIDA STATUTES, | | SECTION 373.62. | | B} THE RAIN SWITCH SHALL BE PLACED ON A STATIONARY | | STRUCTURE MINIMUM OF 5-FOOT (1524MM) CLEARANCE FROM | | OTHER OUTDOOR EQUIPMENT, FREE AND CLEAR OF ANY TREE | | CANOPY OR OTHER OVERHEAD OBSTRUCTIONS, AND ABOVE THE | | HEIGHT OF THE SPRINKLER COVERAGE. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|