Plan Review Notes For Permit 07080847
Permit Number 07080847
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-28 16:36:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)THE NOA PROVIDED IS TO CONTAIN THE FIRST
 SHEETS INCLUDING COMPONENT DESCRIPTIONS (APPROXIMATELY
 7 PAGES).
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS. TWO DIFFERENT INCOMPLETE ASSEMBLIES WERE
 PROVIDED.ONE REFERS TO GENERAL LIMITATION #9, MUST
 REFER TO GENERAL LIMITATION #7.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  