Plan Review Notes For Permit 07080821 |
Permit Number |
07080821 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-10-03 15:45:51 | ***DENIED*** | | | | COMMENTS FROM FIRST FIRE REVIEW HAVE NOT BEEN | | ADDRESSED: | | | | THE PLAN AS SUBMITTED SHOWS THE ALARM PANEL THAT IS TO | | BE INSTALLED. WHAT IS NEEDED IS THE PLAN TO SHOW THE | | LOCATION (FLOOR PLAN) OF THE OBSELETE PANEL AND THE | | LOCATION OF THE NEW PANEL AND ANY OTHER NEWLY | | ASSOCIATED DEVICES/EQUIPMENT TO BE INSTALLED. | | | | THIS REVIEW COMMENT WAS TAKEN DIRECTLY FROM THE FIRST | | FIRE REVIEW. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 | | |
|