2007-08-24 16:27:15 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)ENGINEER'S SPECIFICATION FOR ZONE 3 IS INCORRECT. | | USING "COMMON SENSE"; IF THE ASSEMBLY MEETS A MAXIMUM | | PRESSURE OF -60, HOW CAN THE SAME ASSEMBLY MEET THE | | PRESSURE OF -89?SEE ENGINEER'S CALCULATIONS; ENGINEER | | IS COUNTING ONLY ONE ROW OF FASTNERS IN THE FIELD | | RATHER THAN TWO ROWS.THERE ARE 152.67 FASTENERS PER | | SQUARE, NOT 101.7.PLEASE REVISE CALCULATIONS AND | | SPECIFICATION.A SET HAS BEEN RETAINED. | | | | 2.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS | | REQUIRED TO BE ON EACH SHEET. | | | | |
|