Date |
Text |
2008-03-05 20:14:25 | ** DENIEDREVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS WHICH WERE OK ON PREVIOUS |
| REVIEW HAVE NOW BEEN CHANGED AND DID NOT COORDINATE AND |
| REVISE OTHER SHEETS. PLEASE SEE THE FOLLOWING COMMENTS |
| |
| 1) NOTE:PLEASE SEE THE SCOPE OF WORK HAS CHANGED AND |
| LIGHTING FIXTURE TYPES AND COUNTS HAVE CHANGED YET THE |
| LIGHTING PERFORMANCE CALCULATIONS WERE NOT REVISED. |
| PLEASE SEE FOR EXAMPLE ONLY 3-TYPE A FIXTURES SHOWN IN |
| LP CALCULATIONS. |
| PLEASE SEE THE A FIXTURES ARE NOW 3-32 W ? |
| PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE PROVISO |
| FOR SOME ROOMS WHICH DO REQUIRED AUTOMATED LIGHTING |
| CONTROLS PER 13-415.1.ABC.1.2 EVEN IF THE BUILDING IS |
| UNDER 5K SQFT. PLEASE SEE ROOMS IN SECTION GIVEN WILL |
| REQUIRE OCCUPANCY SENSORS. |
| ** THIS WAS CONFIRMED WITH THE FLORIDA BUILDING |
| COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS. |
| |
| 3) NOTE: ** PLEASE KNOW ANY AREAS IN WHICH EXISTING |
| WIRING IS EXPOSED, DOES NOT MEET CODE, UNSAFE, WATER |
| DAMAGED ETC WILL REQUIRE RE-WIRE UP TO CURRENT CODE. |
| PLEASE SEE MOST OF THE AREAS ARE SHOWN AS NEW TO MEET |
| CURRENT CODES, HOWEVER MANY ARE SHOWN AS EXISTING. |
| AREAS WHICH ARE NOT SAFE ETC WILL BE REQUIRED TO BE |
| BROUGHT UP TO CODE. |
| ** THIS IS GIVEN FOR INFORMATIONAL PURPOSE. |
| BASED ON THE PICTURES AND CONDITIONS AT SITE |
| REVIEWER/OFFICE IS GIVING NOTICE FOR AREAS OF CONCERN |
| WHICH ARE NOT MENTIONED ON PLANS. |
| ANY ITEMS WHICH MAY BE IN QUESTION FOR LIFE SAFETY/ |
| PROPERTY HAZARD WHICH ARE KNOWN TO CONTRACTOR OR DESIGN |
| PROFESSIONALS NEEDS TO BE ADDRESSED ON PLANS AND IS THE |
| RESPONSIBILITY OF SUCH INDIVIDUALS. |
| FS 481, 471, 489 |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |