2008-07-31 09:43:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** RE-STAMP DENIED **
  
 1) WHEN MASTER PERMIT #07080669 WAS APPLIED FOR THEIR
 WAS NO MECHANICAL WORK TO BE DONE. A MECHANICAL
 SUB-PERMIT WAS OBTAINED A YEAR LATTER #08070445 AND DID
 NOT PAY THE CORRECTFEES, PLEASE CHECK ALL MECHANICAL
 WORK BEING DONE AND ADJUST THE VALUE TO MECHANICAL
 PERMIT #08070445, THE VALUE ON THE PERMIT MUST BE
 ADJUSTED TO THE FAIR MARKET VALUE (REPLACEMENT VALUE)
 FOR THE A/C WORK, WITH ALL MATERIALS AND LABOR. IF THE
 VALUE IS NOT ADJUSTED THEN THE CITY WILL NEED TO ADJUST
 IT USING THE MARSHALL & SWIFT NATIONAL VALUATION
 SERVICE, PER 2004 WPB AMEND. 108.3.
  
 2) THE MECHANICAL INFORMATION ON THE REVISED PLAN IS
 UPSIDE-DOWN FROM THE FLOOR PLAN, PLEASE CORRECT.
  
 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS NEW
 AND REPLACE EXISTING FLEX AND GRILL, PER 2004 FBC
 106.3.5.
  
 4) THE MECHANICAL INFORMATION ON THE PLAN IS DIFFICULT
 TO DETERMINE FROM THE FLOOR PLAN INFORMATION ON THE
 PLAN. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1. PLEASE CORRECT.
  
 5) THIS RE-STAMP IS ACTUALLY A REVISION, THE FEE FOR
 THE REVISION HAS BEEN ADJUSTED, PLEASE PAY.
  
 6) THE REVISED PLAN NEEDS TO BE SIGNED AND SEALED BY
 THE ARCHITECT (ROBERT L. BELL), PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]