Plan Review Notes
Plan Review Notes For Permit 07080669
Permit Number 07080669
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-17 17:12:00** PROVISO **
  
 1) NOTE: PLEASE SEE THE LOUNGE AND TRAINING ROOMS WILL
 REQUIRE LIGHTING CONTROLS WHICH WILL AUTOMATICALLY TURN
 OFF LIGHTING WITHIN 30MINS OF THE OCCUPANT LEAVING THE
 SPACE.
 PLEASE SEE 13-415.1.ABC.1.2
 THIS WAS CONFIRMED WITH THE FLORIDA BUILDING COMMISSION
 SINCE THE LAST REVIEW. THESE AUTOMATED LIGHTING
 CONTROLS ARE REQUIRED EVEN IN BUILDINGS LESS THAN 5K SQ
 FT FOR THESE ROOMS AS MENTIONED ABOVE.
  
 ** ELECTRICAL PLANS ARE STAMPED AND DO NOT NEED TO BE
 REVISED UNTIL BEFORE ROUGH ELECTRICAL INSPECTION.
 REVISED PLANS ARE TO BE ON-SITE FOR ELECTRICAL
 INSPECTOR.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  