Plan Review Notes
Plan Review Notes For Permit 07080669
Permit Number 07080669
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-29 08:11:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT 3 THE LOUNGE SINK SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL WITH ELEVATION SHOWING COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 2. SUBMIT A DETAIL WITH ELEVATION FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH
 ALL SUBSECTIONS.
  
 3. SHT 9 IN THE INSTALLATION OR REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SEE
 THE END OF THE RUN UPSTREAM OF SANITARY RISER 4.
  
 4. SHTS 9 & 10 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DESCHARGE
 DOWNSTREAM OF THE WET VENT. (SEE THE LAB SINK SANT.
 RISER 3, AS WELL AS THE XRAY & DARKROOM SINK SANT.
 RISER 4. SECTION 909.1.
  
 5. SUBMIT A WATER RISER DIAGRAM SHOWING ALL PIPE SIZES,
 INCLUDING THE WATER MAINS THAT NEW FIXTURES CONNECT TO,
 VALVES ETC. SECTION 106.3.5.1.3(3)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved