Plan Review Notes
Plan Review Notes For Permit 07080669
Permit Number 07080669
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-16 12:16:062007-09-16 12:16:06
  
 ** DENIED **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE ANY CODES RELEVANT FROM OTHER TRADES
 WHICH MAY BE REQUESTED.
  
 2) NOTE: PLEASE SEE MECHANICAL/BUILDING REVIEW COMMENTS
 FOR VALUE OF PROJECT AND SCOPE OF WORK WHICH MAY
 REQUIRE SOME ITEMS TO MEET CHAPTER 13 FOR OTHER THAN
 ELECTRICAL.
 THE VALUE EXCEEDS THE 30% AS STATED FOR RENOVATIONS.
 THIS IS FOR INFORMATION ONLY, PLEASE SEE NEXT COMMENT
 FOR ELECTRICAL.
  
 3) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND AS
 SUBMITTED INCLUDING FIXTURES TO BE OWNER SELECTED. THE
 ONLY ACCURATE WAY TO FIGURE THE CALCULATIONS FOR
 LIGHTING PERFORMANCE IS TO PROVIDE ALL INFORMATION.
 (THIS CAN ALWAYS BE REVISED IF AN OWNER WOULD LIKE TO
 CHANGE A FIXTURE TYPE AT A LATER DATE).
 PLEASE BE SURE TO PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE LEGEND.
 PLEASE SEE FOR EXAMPLE THERE IS A FIXTURE
 (HAND-WRITTEN) ON PLANS WHICH CALL FOR A 40W
 FLUORESCENT HOWEVER THIS IS NOT ON THE LEGEND? PLEASE
 SEE 13-415.2, 13-415.1.B, 13-415.1.C. PLEASE COMPLETE.
  
 4) NOTE: PLEASE LABEL ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. THERE ARE SOME ITEMS WHICH NEED TO DETERMINED
 CODE COMPLIANCE FOR EXAMPLE AS X-RAY ROOMS,
 EXAM/PATIENT CARE ROOMS WHICH CAN NOT BE DETERMINED AT
 THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE BE SURE THE PANEL SCHEDULE AND
 CIRCUITING CORRELATE WITH ALL ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE NEC 408.4 WHICH REQUIRES ALL
 CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. EXAMPLE: EXAM RM #3 RECEPTS,LIGHTING RM
 102, 105 ETC.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN FROM THE NEC
 COMMENTARY.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE INCLUDE NOTES FOR REDUNDANT GROUNDING
 AS REQUIRED FOR ALL PATIENT CARE AREAS AS DEFINED UNDER
 NEC 517 AND 517.13 AND 517.17.
 PLEASE ADJUST PLANS.
  
 7) NOTE: PLEASE VERIFY AND INDICATE NEW OR EXISTING
 DISCONNECTS FOR A/C EQUIPMENT PER 440.11
 PLEASE VERIFY NEW OR EXISTING GFI RECEPTACLE(S) FOR A/C
 EQUIPMENT. 210.63,210.8B
 ** IT IS KNOWN THAT PLANS CALL FOR A/C WORK TO BE DONE
 BY OTHERS HOWEVER DUE TO THE EXTEND OF THE SCOPE OF
 WORK AND LEVEL OF ALTERATION FOR THE FBC EXISTING
 BUILDING CODE, THESE SHOULD BE VERIFIED AND INDICATED
 AS THE EXISTING MAY NOT MEET CODE OR BE SAFE. PLEASE
 KNOW THIS CAN BE GONE OVER ON PHONE IF NEEDED FOR BEST
 POSSIBLE WAY TO INDICATE.
  
 8) NOTE: PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN
 CIRCUIT PER 600.5.
 PLEASE ADJUST LOAD CALCULATIONS.
  
 9) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED
 ARE NOT COMPLETE AT THIS TIME.
 PLEASE SEE 220.12,220.14,220.42,220.44 ETC
 PLEASE SEE THAT ANY CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%.
 215.3, 230.42.
 PLEASE SEE 422.13 OF THE 2005 NEC AS THE LOAD FOR WATER
 HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS AND NEED TO
 BE SHOWN AT 125%.
 PLEASE ADJUST.
  
 10) NOTE: PLEASE CLARIFY NOTE #1 ON ELECTRICAL LIGHTING
 PLANS WHICH STATES LIGHTING DEVICES FOR SENSOR TYPE,
 BUT THE NOTE COULD NOT BE LOCATED ON PLANS AND FOR THE
 INTENT OF DESIGN WHICH IS BEING PROPOSED.
  
 11) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS.
 PLEASE SEE FOR EXAMPLE THERE ARE SEVERAL EMERGENCY AND
 EXIT LIGHTS WHICH ARE SHOWN WITH OUT CIRCUITING. PLEASE
 SEE 700.12F AS THE FIXTURES ARE REQUIRED TO BE
 CIRCUITED TO THE OTHER BRANCH CIRCUITS FOR NORMAL
 LIGHTING IN ANY ONE AREA.
  
 12) NOTE: PLEASE SEE NFPA-101 2003 7.8 AND 7.9 AS
 BATTERY BACK FIXTURE OF SOME TYPE FOR STAIR AREA
 LEADING TO THE PUBLIC RIGHT OF WAY IS REQUIRED. PLEASE
 KNOW THE LEVEL UNDER NORMAL IS 10FT CANDLES AND 1FT
 CANDLE UNDER EMERGENCY. 7.8.1.3, 7.9.2.2 PLEASE SEE FAC
 61G15-33.004
  
 13) NOTE: PLEASE KNOW THAT NO HAND-DRAWN CHANGES ARE
 PERMITTED TO PLANS BY PEN OR PENCIL.
 PLEASE BE SURE ANY CHANGES ARE DONE BY THE DESIGNER OF
 RECORD.
 FS 471.025, 481.221
  
 14) NOTE: PLEASE SHOW LOCATION OF THE SERVICE AS THIS
 IS NOT BEING SHOWN ON BUILDING ??
 IS THE SERVICE LOCATED ON BUILDING?
 NEED TO VERIFY 230.70,230.71,230.72,230.76,230.79,
 225.31-225.39
 FBC 106.3.5.1.2
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved