Date |
Text |
2007-09-16 12:16:06 | 2007-09-16 12:16:06 |
| |
| ** DENIED ** |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE SEE ANY CODES RELEVANT FROM OTHER TRADES |
| WHICH MAY BE REQUESTED. |
| |
| 2) NOTE: PLEASE SEE MECHANICAL/BUILDING REVIEW COMMENTS |
| FOR VALUE OF PROJECT AND SCOPE OF WORK WHICH MAY |
| REQUIRE SOME ITEMS TO MEET CHAPTER 13 FOR OTHER THAN |
| ELECTRICAL. |
| THE VALUE EXCEEDS THE 30% AS STATED FOR RENOVATIONS. |
| THIS IS FOR INFORMATION ONLY, PLEASE SEE NEXT COMMENT |
| FOR ELECTRICAL. |
| |
| 3) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND AS |
| SUBMITTED INCLUDING FIXTURES TO BE OWNER SELECTED. THE |
| ONLY ACCURATE WAY TO FIGURE THE CALCULATIONS FOR |
| LIGHTING PERFORMANCE IS TO PROVIDE ALL INFORMATION. |
| (THIS CAN ALWAYS BE REVISED IF AN OWNER WOULD LIKE TO |
| CHANGE A FIXTURE TYPE AT A LATER DATE). |
| PLEASE BE SURE TO PLACE ALL FIXTURE DESIGNATIONS ON |
| PLANS AND CORRELATE WITH THE LEGEND. |
| PLEASE SEE FOR EXAMPLE THERE IS A FIXTURE |
| (HAND-WRITTEN) ON PLANS WHICH CALL FOR A 40W |
| FLUORESCENT HOWEVER THIS IS NOT ON THE LEGEND? PLEASE |
| SEE 13-415.2, 13-415.1.B, 13-415.1.C. PLEASE COMPLETE. |
| |
| 4) NOTE: PLEASE LABEL ALL ROOM AND AREA DESIGNATIONS ON |
| PLANS. THERE ARE SOME ITEMS WHICH NEED TO DETERMINED |
| CODE COMPLIANCE FOR EXAMPLE AS X-RAY ROOMS, |
| EXAM/PATIENT CARE ROOMS WHICH CAN NOT BE DETERMINED AT |
| THIS TIME. |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 5) NOTE: PLEASE BE SURE THE PANEL SCHEDULE AND |
| CIRCUITING CORRELATE WITH ALL ROOMS AND AREAS IN WHICH |
| THEY FEED. PLEASE SEE NEC 408.4 WHICH REQUIRES ALL |
| CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| THEY FEED. EXAMPLE: EXAM RM #3 RECEPTS,LIGHTING RM |
| 102, 105 ETC. |
| PLEASE SEE THE FOLLOWING TEXT IS TAKEN FROM THE NEC |
| COMMENTARY. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 6) NOTE: PLEASE INCLUDE NOTES FOR REDUNDANT GROUNDING |
| AS REQUIRED FOR ALL PATIENT CARE AREAS AS DEFINED UNDER |
| NEC 517 AND 517.13 AND 517.17. |
| PLEASE ADJUST PLANS. |
| |
| 7) NOTE: PLEASE VERIFY AND INDICATE NEW OR EXISTING |
| DISCONNECTS FOR A/C EQUIPMENT PER 440.11 |
| PLEASE VERIFY NEW OR EXISTING GFI RECEPTACLE(S) FOR A/C |
| EQUIPMENT. 210.63,210.8B |
| ** IT IS KNOWN THAT PLANS CALL FOR A/C WORK TO BE DONE |
| BY OTHERS HOWEVER DUE TO THE EXTEND OF THE SCOPE OF |
| WORK AND LEVEL OF ALTERATION FOR THE FBC EXISTING |
| BUILDING CODE, THESE SHOULD BE VERIFIED AND INDICATED |
| AS THE EXISTING MAY NOT MEET CODE OR BE SAFE. PLEASE |
| KNOW THIS CAN BE GONE OVER ON PHONE IF NEEDED FOR BEST |
| POSSIBLE WAY TO INDICATE. |
| |
| 8) NOTE: PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN |
| CIRCUIT PER 600.5. |
| PLEASE ADJUST LOAD CALCULATIONS. |
| |
| 9) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED |
| ARE NOT COMPLETE AT THIS TIME. |
| PLEASE SEE 220.12,220.14,220.42,220.44 ETC |
| PLEASE SEE THAT ANY CONTINUOUS LOADS ARE TO BE SHOWN AT |
| 125%. |
| 215.3, 230.42. |
| PLEASE SEE 422.13 OF THE 2005 NEC AS THE LOAD FOR WATER |
| HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS AND NEED TO |
| BE SHOWN AT 125%. |
| PLEASE ADJUST. |
| |
| 10) NOTE: PLEASE CLARIFY NOTE #1 ON ELECTRICAL LIGHTING |
| PLANS WHICH STATES LIGHTING DEVICES FOR SENSOR TYPE, |
| BUT THE NOTE COULD NOT BE LOCATED ON PLANS AND FOR THE |
| INTENT OF DESIGN WHICH IS BEING PROPOSED. |
| |
| 11) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS. |
| PLEASE SEE FOR EXAMPLE THERE ARE SEVERAL EMERGENCY AND |
| EXIT LIGHTS WHICH ARE SHOWN WITH OUT CIRCUITING. PLEASE |
| SEE 700.12F AS THE FIXTURES ARE REQUIRED TO BE |
| CIRCUITED TO THE OTHER BRANCH CIRCUITS FOR NORMAL |
| LIGHTING IN ANY ONE AREA. |
| |
| 12) NOTE: PLEASE SEE NFPA-101 2003 7.8 AND 7.9 AS |
| BATTERY BACK FIXTURE OF SOME TYPE FOR STAIR AREA |
| LEADING TO THE PUBLIC RIGHT OF WAY IS REQUIRED. PLEASE |
| KNOW THE LEVEL UNDER NORMAL IS 10FT CANDLES AND 1FT |
| CANDLE UNDER EMERGENCY. 7.8.1.3, 7.9.2.2 PLEASE SEE FAC |
| 61G15-33.004 |
| |
| 13) NOTE: PLEASE KNOW THAT NO HAND-DRAWN CHANGES ARE |
| PERMITTED TO PLANS BY PEN OR PENCIL. |
| PLEASE BE SURE ANY CHANGES ARE DONE BY THE DESIGNER OF |
| RECORD. |
| FS 471.025, 481.221 |
| |
| 14) NOTE: PLEASE SHOW LOCATION OF THE SERVICE AS THIS |
| IS NOT BEING SHOWN ON BUILDING ?? |
| IS THE SERVICE LOCATED ON BUILDING? |
| NEED TO VERIFY 230.70,230.71,230.72,230.76,230.79, |
| 225.31-225.39 |
| FBC 106.3.5.1.2 |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| THIS REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |