Plan Review Notes For Permit 07080657 |
Permit Number |
07080657 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-04 14:37:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) PROVIDE OUT-SIDE AIR CALCULATIONS ON MECHANICAL | | PLANS, SEE 2004 MECH. 401.2. | | | | 2) PLEASE SUBMIT PRODUCT APPROVAL OR APPLY FOR A LOCAL | | PRODUCT APPROVAL FOR PER-ENGINEERED CONDENSER STANDS, | | SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND | | FAC 9B-72.010(31)(G). | | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|