2007-08-21 15:05:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
  
 1.)CONTRACTOR IS TO PROVIDE THE FOLLOWING INFORMATION
 ON THE APPLICATION, SEE POLICY (AVAILABLE IN THE
 LOBBY); MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE,
 AREA OF EACH ROOF TYPE
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 3.)FOR THE FLAT DECK, INDICATE ON TABLE A WHICH
 SYSTEM YOU WILL USE..ALSO INDICATE WHICH FASTENER YOU
 ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 4.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FS471.025 (SHEET A1).
  
 5.)ALL INFORMATION REQUIRED BY FAC61G15-23.002
 REQUIRED ON EACH SHEET (ENGINEERING PREPARED BY
 PISTORINO & ALAM CONSULTING ENGINEERS INC, 4397).
  
 6.)DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 7.)DECLARE GOVERNING CODE, FBC*106.
  
 8.)PROVIDE SHEET A1 IN A LARGER, LEGIBLE FORMAT,
 FBC*106.
  
 9.)PROVIDE BUILDING HEIGHT.