2008-07-24 16:07:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE C/U #TTX048C100A AND A/H/U #TWE048P
 COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE,
 PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004
 FBC 13-407.1.ABC.3.1.1.
  
 2) PLEASE ADD TO THE MECHANICAL PLAN, A DETAIL FOR
 HANGING THE KITCHEN HOOD TO THE CEILING, AND A DETAIN
 FOR SECURING THE EXHAUST FAN ROOF CURB TO WITHSTAND 140
 MPH WINDS, PER 2004 FBC 1609.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR THE
 24X16 AND 12X16 WALL LOUVERS, SEE FS 553.842(1) AND FAC
 RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  