Plan Review Notes
Plan Review Notes For Permit 07080606
Permit Number 07080606
Review Stop E
Sequence Number 3
Notes
Date Text
2008-07-31 14:39:27** DENIED3RD REVIEW **
  
 ** THERE ARE STILL COMMENTS FROM PREVIOUS REVIEW ALONG
 WITH SEVERAL NEW COMMENTS BASED ON NEW INFORMATION NOW
 BEING PROVIDED.
  
  
  
 1) NOTE: PLEASE KNOW THE BASE BUILDING PERMIT #06011130
 WHICH WAS PREVIOUSLY FOR THE SHELL BUILDING HAS BEEN
 EXPIRED DUE TO INACTIVITY UNDER THE FBC 105.3.2 BY
 HAROLD PISKURA
 PERMIT FOR BASE BUILDING NEEDS TO BE RE-APPLIED FOR
 FINALS.
 PLEASE ALSO KNOW AS THE BASE BUILDING DESIGN TEAM IS
 RESPONSIBLE FOR SUCH BUILDING UNTIL SUCH TIME AS
 CERTIFICATE OF COMPLETION OR CERTIFICATE OF OCCUPANCY
 IS ISSUED ALL PLANS FOR PERMITTED WORK WHILE A SHELL
 BUILDING IS UNDER CONSTRUCTION SHALL CONTAIN A *SHOP
 DRAWING* REVIEW STAMP AND SIGNATURE FROM EACH DESIGNER
 ON THEIR RESPECTIVE PAGES BEFORE PERMIT MAY BE ISSUED
 FOR TENANT BUILD OUT.
 FS 471,481. ONCE THE SHELL OBTAINS AS C OF C ETC THEN
 THE PLANS DO NOT NEED TO GO BACK TO THE BASE BUILDING
 DESIGN TEAM.
  
 2) NOTE: PLEASE KNOW AS THE BASE BUILDING/SHELL
 CONTRACTOR IS THE SAME AS APPLIED FOR THIS SCOPE OF
 WORK A LETTER OF UNDERSTANDING IS NOT REQUIRED.
  
 3) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY
 CALCULATIONS ARE BEING SUBMITTED. THE PREVIOUS TWO
 REVIEWS REQUESTED LIGHTING PERFORMANCE CALCULATIONS AND
 THE SPECIFIC CODE SECTIONS GIVEN WERE
 13-415.2.ABC.1.1,.1.2 AN D.1.3. THE CODE SECTIONS FOR
 METHOD OF CALCULATIONS GIVEN WERE 13-400.3.B,
 13-400.3.C. SECTION 13-400.3.A WAS NOT GIVEN AS METHOD
 *A* MAY NOT BE USED.
 PLANS WERE SUBMITTED WITH METHOD *A*. PLEASE SEE THE
 FLORIDA BUILDING CODE 13-400.0.A, 13-101.1.1. PLEASE
 EXPLAIN HOW METHOD *A* MAY BE USED WHEN THIS TENANT
 BUILDING IS NOT A WHOLE BUILDING.
 PLEASE SEE THAT IN ANY CASE THE INFORMATION AS
 SUBMITTED AND SHOWN ON THE INPUT DATA REPORT IS NOT
 COMPLETE NOR DOES IT COORDINATE WITH PLANS IN SEVERAL
 ASPECTS. SOME EXAMPLES WILL BE NOTED BY THIS REVIEWER
 AND PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES AS
 WELL.
 PLEASE SEE 13-103.1. MEETING THE EXCEPTIONS UNDER FS
 471.003 AND THIS SECTION OF THE FBC REQUIRES LICENSED
 DESIGNER.
  
 FOR EXAMPLE:
 THE IDR SHOWS ONLY TWO (2) LIGHT FIXTURES ON THE
 INTERIOR OF THIS SPACE. HOW IS THIS POSSIBLE WHEN IN
 FACT THE PLANS SHOW MANY FIXTURES? THE FACT IS THE ONLY
 TWO FIXTURES SHOWN ARE 2 WATTS EACH. THIS IS NOT
 POSSIBLE AS THE PLANS DO NOT CORRELATE WITH ANY OF
 THIS.
  
 FORE EXAMPLE;
 ONLY ONE WALL UNDER WALLS, NO WINDOWS, NO DOORS, METAL
 BUILDING ETC. THESE WILL BE NOTED BY OTHER TRADES
 HOWEVER ARE GIVEN FOR INFORMATION AT THIS TIME.
  
 4) NOTE: PLEASE KNOW ELECTRICAL SERVICE AS SHOWN ON
 THESE PLANS DOES NOT COORDINATE WITH THE ELECTRICAL
 SERVICE ON THE BASE BUILDING. IN FACT THE ELECTRICAL
 SERVICE ON THE BASE BUILDING WHICH ALREADY HAS A FINAL
 CONTAINS MANY ITEMS WHICH ARE NOT THE SAME.
 MAINS ARE 125 AMP
 THERE IS A HOUSE PANEL NOT SHOWN.
 THE SERVICE SIZE IS NOT 400AMPS.
 THE GROUNDING ELECTRODE SYSTEM IS NOT THE SAME AND
 MEETS 250.50,250.24,250.6 ETC
 PLEASE EXPLAIN HOW THE GUTTER HAS AN EQUAL POTENTIAL IF
 THE NEUTRAL IS FLOATING TO THE FIRST MEANS OF
 DISCONNECT. BASED ON THE CODE AND THE RISER FOR BASE
 BUILDING THE SYSTEM AS SHOWN ON THIS RISER MAY NOT BE
 DONE TO MEET THE CODE.
 PLAN SHOWS THREE DISCONNECTS/MAINS
 215.5, 230.70, 230.71, 230.72, 240.4, 310.16, 250.6,
 250.24 ETC
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF
 EXTERIOR LIGHTING. PLANS MENTIONS TIME CLOCK HOWEVER
 NOT FOR ALL LIGHTS AND ALSO SHOWS STANDARD SINGLE POLE
 SWITCH. MUST MEET ONE OF THE TWO MINIMUMS IN SECTION OF
 CODE GIVEN OR BOTH.
  
 ** BASED ON COMMENTS ABOVE ONE SET OF CALCULATIONS
 ALONG WITH ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 ***AS THERE ARE MANY ASPECTS OF THE BUILDING AND
 CALCULATIONS NOT COMPLETE AT THIS TIME THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  