| 3RD RREVIEW |
| BUILDING PLAN REVIEW |
| PERMIT: 07080606 |
| ADD: 2037 SPRUCE AVE |
| CONT: JHAMTEC CONSTRUCTION |
| TEL: (561)602-0009 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 3RD AUGUST 21, 2008 |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) OK |
| |
| DUE TO THE FACT THAT PERMIT #06011130 IS AN EXPIRED |
| PERMIT AND THE BUILDING DOES NOT HAVE A CERTIFICATE OF |
| OCCUPANCY OR FINAL INSPECTION THE SHALL MEET THE |
| REQUIREMENTS OF THE SECTION BELOW. |
| NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT |
| COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8" DOOR WILL NOT |
| MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE |
| MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE |
| OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING |
| SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW. |
| ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE |
| LOCATED ON THE SHORTEST ROUTE. |
| 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO ALTERED AREAS SHALL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. |
| (A)(I) OK |
| (II) AN ACCESSIBLE ROUTE |
| (III) OK |
| (IIII) OK |
| |
| FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5 |
| CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR |
| OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES, |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE |
| STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), |
| AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 |
| MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND |
| 11-4.3.3 [SEE FIGURE 24 (E)]. |
| |
| 5) OK |
| |
| 6) OK |
| 7) OK |
| |
| **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE |
| SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING. THE |
| PARKING LOT DOES NOT HAVE A FINAL INSPECTION THEREFORE, |
| THE ISSUE OF THE ACCESSIBLE PARKING HAS TO BE |
| ADDRESSED** |
| 8) THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE |
| PARKING PLEASE INDICATE THE HANDICAPPED PARKING AND |
| ACCESS ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING |
| SPACES SERVING A PARTICULAR BUILDING SHALL BE LOCATED |
| ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM |
| ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING |
| FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING, |
| ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST |
| ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN |
| ENTRANCE OF THE PARKING FACILITY. |
| |
| **3RD REQUEST** |
| 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| APPLICABLE. |
| |