2008-03-18 12:01:25 | ** DENIED 2ND REVIEW** |
| |
| ** PLEASE SEE SOME COMMENTS ARE THE SAME FROM PREVIOUS |
| REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE |
| ALSO SEE SOME NEW COMMENTS DUE TO NEW INFORMATION NOW |
| ON PLANS. |
| |
| ** PLEASE NOTE: AS THERE IS INFORMATION STILL NOT YET |
| SUBMITTED FOR REVIEW, A FULL REVIEW CAN NOT BE DONE AND |
| THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT |
| REVIEW. |
| |
| 1) NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE |
| SUBMITTED, NO LIGHTING PERFORMANCE CALCULATIONS ETC. |
| PLEASE SEE 13-400.3.B, 13-400.3.C, 13-415.2, |
| 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| PLEASE SEE 13-412 FOR WATER HEATING SYSTEMS. |
| PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THESE |
| SECTIONS. |
| |
| 2) NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED A RESPONSE |
| LETTER FROM DESIGN PROFESSIONAL IS HELPFUL IN THE |
| REVIEW PROCESS. THERE ARE RESPONSES FOR ALL OTHER |
| TRADES BUT ELECTRICAL. |
| THIS IS ONLY NOTED AS IT MAY HELP THE REVIEW OF SAID |
| PLANS. |
| |
| 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS |
| BEING SHOWN CONNECTED AFTER THE FIRST MEANS OF |
| DISCONNECT ON THE TENANT MAINS?? |
| PLEASE SEE 250.6, 250.524 AS THIS IS NOT PERMITTED. |
| PLEASE SEE THE GE SYSTEM IS ALSO STILL SHOWN TO FOOTER |
| STEEL, IS THIS AN EXISTING SERVICE OR NEW? IS THERE AND |
| EXISTING GROUNDING ELECTRODE CONNECTED TO FOOTER? |
| 250.50 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 4) NOTE: PLEASE SEE 250.104 AS THE GAS PIPE SHOULD NOT |
| BE PART OF THE GROUNDING ELECTRODE SYSTEM. IS THIS A |
| BOND ONLY? |
| |
| 5) NOTE: PLEASE SEE THE SHOW WINDOWS WILL REQUIRE |
| RECEPTACLES ABOVE WINDOW PER 210.62 |
| PLEASE ADJUST LOAD CALCULATIONS PER 220.43 |
| |
| 6) NOTE: PLEASE BE SURE TO ADJUST LOAD CALCULATIONS FOR |
| MIXED USE AS UPSTAIRS IS SHOWN AS APARTMENT. |
| 220 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |