Plan Review Notes
Plan Review Notes For Permit 07080606
Permit Number 07080606
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-18 12:01:25** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME COMMENTS ARE THE SAME FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 ALSO SEE SOME NEW COMMENTS DUE TO NEW INFORMATION NOW
 ON PLANS.
  
 ** PLEASE NOTE: AS THERE IS INFORMATION STILL NOT YET
 SUBMITTED FOR REVIEW, A FULL REVIEW CAN NOT BE DONE AND
 THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT
 REVIEW.
  
 1) NOTE: PLEASE SEE NO ENERGY CALCULATIONS WERE
 SUBMITTED, NO LIGHTING PERFORMANCE CALCULATIONS ETC.
 PLEASE SEE 13-400.3.B, 13-400.3.C, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-412 FOR WATER HEATING SYSTEMS.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THESE
 SECTIONS.
  
 2) NOTE: PLEASE KNOW ALTHOUGH NOT REQUIRED A RESPONSE
 LETTER FROM DESIGN PROFESSIONAL IS HELPFUL IN THE
 REVIEW PROCESS. THERE ARE RESPONSES FOR ALL OTHER
 TRADES BUT ELECTRICAL.
 THIS IS ONLY NOTED AS IT MAY HELP THE REVIEW OF SAID
 PLANS.
  
 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS
 BEING SHOWN CONNECTED AFTER THE FIRST MEANS OF
 DISCONNECT ON THE TENANT MAINS??
 PLEASE SEE 250.6, 250.524 AS THIS IS NOT PERMITTED.
 PLEASE SEE THE GE SYSTEM IS ALSO STILL SHOWN TO FOOTER
 STEEL, IS THIS AN EXISTING SERVICE OR NEW? IS THERE AND
 EXISTING GROUNDING ELECTRODE CONNECTED TO FOOTER?
 250.50
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE 250.104 AS THE GAS PIPE SHOULD NOT
 BE PART OF THE GROUNDING ELECTRODE SYSTEM. IS THIS A
 BOND ONLY?
  
 5) NOTE: PLEASE SEE THE SHOW WINDOWS WILL REQUIRE
 RECEPTACLES ABOVE WINDOW PER 210.62
 PLEASE ADJUST LOAD CALCULATIONS PER 220.43
  
 6) NOTE: PLEASE BE SURE TO ADJUST LOAD CALCULATIONS FOR
 MIXED USE AS UPSTAIRS IS SHOWN AS APARTMENT.
 220
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717