Plan Review Notes
Plan Review Notes For Permit 07080606
Permit Number 07080606
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-04 14:50:592ND RREVIEW
 BUILDING PLAN REVIEW
 PERMIT: 07080606
 ADD: 2037 SPRUCE AVE
 CONT: JHAMTEC CONSTRUCTION
 TEL: (561)602-0009
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND APRIL 2, 2008
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
  
 NOTE: THE REVISION #1 TO THE DOOR ON SHEET A-1 DOES NOT
 COMPLY WITH FIGURE 24. A 2'-8" X 6'- 8"DOOR WILL NOT
 MEET THE 32" MINIMUM REQUIREMENT. THE DISTANCE SHALL BE
 MEASURED FROM THE INSIDE FACE OF THE DOOR TO THE FACE
 OF THE DOOR STOP. PLEASE TAKE A LOOK AT THE DRAWING
 SUBMITTED ON SHEET A-1. SEE CODE SECTION MENTION BELOW.
 ACCESSIBLE PARKING SPACES SERVING BUILDINGS SHALL BE
 LOCATED ON THE SHORTEST ROUTE.
 4) 11-4.1.6(2) DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 % OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
 (A)(I) OK
 (II) AN ACCESSIBLE ROUTE
 (III) OK
 (IIII) OK
  
 FRONT ENTRY DOOR, A PAIR OF 5'-0" DOORS, SEE11-4.13.5
 CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM CLEAR
 OPENING OF 32 INCHES WITH THE DOOR OPEN 90 DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE
 STOP [SEE FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C),
 AND FIGURE 24 (D)]. OPENINGS MORE THAN 24 INCHES (610
 MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 AND
 11-4.3.3 [SEE FIGURE 24 (E)].
  
 5) OK
  
 **NOTE: THE UL NUMBER FOR THE FLOOR CEILING ASSEMBLY
 FOR THE BASE BUILDING IS L557, SO PLEASE INDICATE THIS
 NUMBER ON THE DRAWINGS.
 6) PLEASE PROVIDE A DETAIL INDICATING THE FIRE RATING
 AT CEILING BETWEEN THIS MERCANTILE TENANT AND THE R-3
 RESIDENCE LOCATED ON THE SECOND FLOOR? ALSO PROVIDE
 WHAT TYPE OF FIRE STOPPING MATERIALS WILL BE USED
 AROUND ANY PIPES THAT PENETRATE THE CEILING FLOOR
 ASSEMBLY SYSTEM? 106.1.2*
  
 7) OK
  
 **NOTE: ACCESSIBLE PARKING SHALL BE LOCATED ON THE
 SHORTEST ROUTE TO THE ENTRANCE OF THE BUILDING.**8)
 THE SITE PLAN DOES NOT INDICATE ANY ACCESSIBLE PARKING
 PLEASE INDICATE THE HANDICAPPED PARKING AND ACCESS
 ISLE. 11-4.6.2 LOCATION. ACCESSIBLE PARKING SPACES
 SERVING A PARTICULAR BUILDING SHALL BE LOCATED ON THE
 SHORTEST SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. IN PARKING
 FACILITIES THAT DO NOT SERVE A PARTICULAR BUILDING,
 ACCESSIBLE PARKING SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN ACCESSIBLE PEDESTRIAN
 ENTRANCE OF THE PARKING FACILITY.
  
 **2ND REQUEST**
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]