Plan Review Notes
Plan Review Notes For Permit 07080606
Permit Number 07080606
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-13 06:10:41DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE THE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL &
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY WPB FOR REVIEW. REVIEWED &
 STAMPED PLANS SHALL BE INSERTED INTO EACH SET OF PLANS
 SUBMITTED FOR REVIEW WITH THE TWO PAGE "SPECIFICATION
 WORKSHEETS" ATTACHED TO THE SHEETS STAMPED/REVIEWED BY
 DBPR. SECTION 102.2.1.
  
 2. SHT A-1 DETAIL FOR THE TOILET ROOM IS INDICATED AS
 DETAILD-1/A-3, BUT SHEET A-3 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT A-2 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ___FOR LAV:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
  
 4. SHT A-2 FINISH. WALLS WITHIN 2' OF THE W/C SHALL BE
 A SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET ABOVE
 THE FLOOR PER SECTION 1210.2. PLANS SHOW FINISH
 DRYWALL. PLEASE SHOW COMPLIANCE.
  
 5. SHT P-1 A CLEANOUT IS REQUIRED NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING SEWER PER SECTION
 708.3.5. A TWO WAY CLEANOUT WILL ENABLE CLEANOUT IN THE
 BUILDING AND OUT TO THE SEWER.
  
 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561)
 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS
 (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS
 (561) 822-2287. A PRINTED DETERMINATION SHALL BE
 PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR
 SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F).
  
 7. SHT P-2 SANITARY ISOMETRIC. A VENT IS REQUIRED FOR
 THE MOP SINK. SECTION 901.2.1.
  
 8. SHT P-2 SANITARY ISOMETRIC. PLEASE INDICATE THE USE
 OF THE FLOOR SINK IN THE MIDDLE OF THE FLOOR. IF THIS
 IS TO DRAIN THE FLOOR, A FLOOR DRAIN IS REQUIRED. FLOOR
 SINKS ARE FOR INDIRECT WASTE. SECTIONS 106.1.2 &
 802.3.
  
 9. SHT P-2 THE WATER ISOMETRIC DOES NOT REFLECT THE
 FLOOR PLAN AT THE MOP SINK & AT THE TOILET ROOM. PLEASE
 CORRELATE. SECTION 106.1.1. PLEASE MAKE SURE RISER
 DIAGRAM REFLECTS THE FLOOR PLAN.
  
 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE
 INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE
 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE.
 PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW
 ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH
 APPLIANCE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER
 COMMENT "A" ADDRESSED.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION
 409.1.3. PLEASE INDICATED ON PLANS.
  
 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR
 DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS
 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved