Date |
Text |
2007-10-13 06:10:41 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| MUNICIPAL CODE WPB |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ROUTE THE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL & |
| RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO |
| RESUBMITTING TO THE CITY WPB FOR REVIEW. REVIEWED & |
| STAMPED PLANS SHALL BE INSERTED INTO EACH SET OF PLANS |
| SUBMITTED FOR REVIEW WITH THE TWO PAGE "SPECIFICATION |
| WORKSHEETS" ATTACHED TO THE SHEETS STAMPED/REVIEWED BY |
| DBPR. SECTION 102.2.1. |
| |
| 2. SHT A-1 DETAIL FOR THE TOILET ROOM IS INDICATED AS |
| DETAILD-1/A-3, BUT SHEET A-3 HAS NOT BEEN SUBMITTED. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 3. SHT A-2 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR |
| W/C: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| ___FOR LAV: |
| A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| D. 11-4.19.6 MIRRORS |
| |
| 4. SHT A-2 FINISH. WALLS WITHIN 2' OF THE W/C SHALL BE |
| A SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET ABOVE |
| THE FLOOR PER SECTION 1210.2. PLANS SHOW FINISH |
| DRYWALL. PLEASE SHOW COMPLIANCE. |
| |
| 5. SHT P-1 A CLEANOUT IS REQUIRED NEAR THE JUNCTION OF |
| THE BUILDING DRAIN AND THE BUILDING SEWER PER SECTION |
| 708.3.5. A TWO WAY CLEANOUT WILL ENABLE CLEANOUT IN THE |
| BUILDING AND OUT TO THE SEWER. |
| |
| 6. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| UTILITY DEPT., INDUSTRIAL PRETREATMENT, ENVIRONMENTAL |
| COMPLIANCE. PLEASE CONTACT EITHER RODNEY COMPO, (561) |
| 822-2272, E-MAIL [email protected] OR CALVIN WILLIAMS |
| (561) 822-2284, E-MAIL CWILLIAMS @WPB.ORG. THEIR FAX IS |
| (561) 822-2287. A PRINTED DETERMINATION SHALL BE |
| PRODUCED AND SUBMITTED WITH PLANS SHOWING INTERCEPTOR |
| SIZE APPROVAL. ARTICLE III SECTION 90-124(7)(F). |
| |
| 7. SHT P-2 SANITARY ISOMETRIC. A VENT IS REQUIRED FOR |
| THE MOP SINK. SECTION 901.2.1. |
| |
| 8. SHT P-2 SANITARY ISOMETRIC. PLEASE INDICATE THE USE |
| OF THE FLOOR SINK IN THE MIDDLE OF THE FLOOR. IF THIS |
| IS TO DRAIN THE FLOOR, A FLOOR DRAIN IS REQUIRED. FLOOR |
| SINKS ARE FOR INDIRECT WASTE. SECTIONS 106.1.2 & |
| 802.3. |
| |
| 9. SHT P-2 THE WATER ISOMETRIC DOES NOT REFLECT THE |
| FLOOR PLAN AT THE MOP SINK & AT THE TOILET ROOM. PLEASE |
| CORRELATE. SECTION 106.1.1. PLEASE MAKE SURE RISER |
| DIAGRAM REFLECTS THE FLOOR PLAN. |
| |
| 10. SHT P-2 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED FOR PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - NOT ALL CUT SECTION LENGTHS ARE |
| INDICATED. SEE ALL SECTIONS FROM THE METER TO WHERE THE |
| 22 FT LENGTH, AND THE RISER LENGTHS TO EACH APPLIANCE. |
| PLEASE SHOW THE LENGTH OF ALL CUT SECTIONS.--SHOW |
| ALL PIPE SIZES UP THRU THE SHUT OFF VALVE OF EACH |
| APPLIANCE. |
| |
| B. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED AFTER |
| COMMENT "A" ADDRESSED. |
| |
| C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| D. SHUT OFF VALVES SHALL BE ACCESSIBLE PER SECTION |
| 409.1.3. PLEASE INDICATED ON PLANS. |
| |
| 11. ALL MECHANICAL, PLUMBING & ELECTRICAL SHEETS. THE |
| CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED FOR |
| DESIGN SERVICES MEP LLC. FAC 61G15-23.002(2) & FS |
| 471.025. PLEASE SHOW CA NUMBER ON ALL SHEETS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |