2007-09-26 19:04:22 | 1- PLEASE PROVIDE A FULL SET OF PLANS FOR REVIEW | | ,MISSING PAGE A-3, A CEILING DETAIL, AND 2ED FLOOR | | MECHANICAL PLANS . | | 2- PLEASE REFER TO NOTE 5 ON PAGE SP-1 , 1HR RATING | | BETWEEN GROUND FLOOR AND 2ED FLOOR . PLEASE REFER TO | | TABLE 302.3.2 REQUIRED SEPARATIONS OF OCCUPANCIES 2004 | | FBC | | 3-CONDENSER MUST BE 10 FT AWAY FROM MAKE UP AIR TO | | HOOD | | 4- FIRE DAMPERS ARE REQUIRED IN ALL DUCT PENETRATIONS | | THROUGH THE CEILING. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|