Plan Review Notes
Plan Review Notes For Permit 07080606
Permit Number 07080606
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-18 15:41:08******DENIED*****
  
 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE LAYOUT OF THE PROPOSED 1ST FLOOR PLAN (SHEET
 A-1) DOES NOT CORRELATE WITH LAYOUT SHOWN ON SITE PLAN
 (SHEET SP-1) .AMEND DIRECTIONAL LEGEND.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE COOKING HOOD SYSTEM AND FOR THE
 FIRE SUPPRESSION SYTEM FOR THE HOOD.NFPA 96 - 2001
 EDITION - SHALL BE REFERENCED.
  
 4.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 5.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM, AS PER WEST PALM BEACH FIRE PREVENTION.
  
 6.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.PLEASE ACKNOWLEDGE THAT THE NUMERICAL ADDRESS SHALL
 BE POSTED ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 SPRUCE AVENUE.THE ADDRESS IS TO BE DISPLAYED PRIOR,
 DURING, AND AFTER CONSTRUCTION OPERATIONS.AS PER WEST
 PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  