Plan Review Notes For Permit 07080606 |
Permit Number |
07080606 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-18 15:41:08 | ******DENIED***** | | | | 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.THE LAYOUT OF THE PROPOSED 1ST FLOOR PLAN (SHEET | | A-1) DOES NOT CORRELATE WITH LAYOUT SHOWN ON SITE PLAN | | (SHEET SP-1) .AMEND DIRECTIONAL LEGEND. | | | | 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | INSTALLATION OF THE COOKING HOOD SYSTEM AND FOR THE | | FIRE SUPPRESSION SYTEM FOR THE HOOD.NFPA 96 - 2001 | | EDITION - SHALL BE REFERENCED. | | | | 4.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | INSTALLATION OF THE FIRE ALARM SYSTEM. | | | | 5.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | ALARM, AS PER WEST PALM BEACH FIRE PREVENTION. | | | | 6.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 7.PLEASE ACKNOWLEDGE THAT THE NUMERICAL ADDRESS SHALL | | BE POSTED ON THE APPROPIATE EXTERIOR ELEVATION FRONTING | | SPRUCE AVENUE.THE ADDRESS IS TO BE DISPLAYED PRIOR, | | DURING, AND AFTER CONSTRUCTION OPERATIONS.AS PER WEST | | PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6" | | IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|