2007-09-13 07:30:29 
  
 ** DENIED **
  
 1) NOTE: PLEASE DECLARE IF THIS IS A CHANGE IN
 OCCUPANCY OR USE ON PLANS.
 DOES NOT INDICATE THE PREVIOUS USE BEING NEW RESTAURANT
 BUILD OUT AND APPEARS TO BE A NEW BUILD OUT OF
 RESTAURANT.
  
 2) NOTE: PLEASE INCLUDE THE ADDRESS ON THE MEP PLANS AS
 SHOWN ON THE ARCHITECTURAL SHEETS.
 FAC 61G15-23.002
 FBC 106.1.2, 110.1.2
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ONLY INDICATE
 ONE A/C SYSTEM BEING FIGURED INTO LOAD CALCULATIONS AND
 PANEL, YET THE ARCHITECTURAL SHEET SP-1 INDICATES AN
 EXISTING A/C SYSTEM WITH A NEW ONE BEING ADDED? NEC,
 220, FBC 106.3.5.1.2
  
 4) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE
 ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY
 CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B,
 13-415.1.C.
 PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED PER 13-415.2. PLEASE SEE
 TABLES415.2.C.1, 415.2.B.1.
 PLEASE SUBMIT A FIXTURE LEGEND ON PLANS WITH
 INFORMATION ON FIXTURE TYPES WATTAGE ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS
 AND SERVICE EQUIPMENT AS SHOWN ON RISER.
 110.9.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE INDICATE *FLOATING NEUTRAL* REQUIRED AT
 THE METERS.
 250.6, 250.24
  
 7) NOTE: PLEASE SEE NFPA-96 FOR SHUT DOWN OF ALL
 ELECTRICAL UNDER HOOD.
 PLEASE INDICATE THE REQUIRED SHUNT TRIP BREAKERS.
 PLEASE SEE CHAPTERS 9 AND 10. PLEASE BE SURE TO SEE ANY
 MECHANICAL REVIEW COMMENTS.
  
 8) NOTE: PLEASE PROVIDE THE MINIMUM ADA LEVELS FOR FIRE
 ALARMS DEVICES PER 11-4.28.1, .2 AND .3(4).
  
 9) NOTE: PLEASE CORRELATE PLANS WITH RISER. PLANS ONLY
 INDICATE ONE METER AND ONE MAIN DISCONNECT.
 PLEASE INCLUDE ALL EQUIPMENT AS SHOWN ON RISER ON THE
 PLANS WITH THE LOCATIONS.
 100.26, FBC 106.1.2
  
 10) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING
 STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS
 IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN
 EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING
 THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS
 THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL
 INTEGRITY OF THE FOUNDATION.
 (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS
 IS BEING SPECIFIED.)
 PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50,
 250.104.
  
 11) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS
 REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW
 THIS WAS A CHANGE IN THE 2005 NEC.
 230.42, 215.3, 422.13 ETC
  
 12) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE.
 THE PANEL SCHEDULE SHOWS PANEL WITH A 150AMP MAIN
 CIRCUIT BREAKER, AND RISER SHOWS THIS WITH A 200AMP
 MAIN CIRCUIT BREAKER.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN
 KITCHEN AREAS ARE REQUIRED TO BE GFI/GFI PROTECTED
 WHETHER OR NOT THESE ARE FEEDING COUNTER SPACE AREAS.
 PLEASE KNOW THIS WOULD INCLUDE REFRIGERATION EQUIPMENT
 ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-09-13 06:58:412007-09-13 06:58:41
  
 IN REVIEW
2007-09-12 20:31:362007-09-12 20:31:36
  
 REVIEW TO BE COMPLETED 9/13, NOTES TO FOLLOW.
2007-09-12 19:58:392007-09-12 19:58:39
  
 REVIEW COMMENCED
2007-09-11 20:09:202007-09-11 20:09:20
  
 IN ELEC FOR REVIEW.