2007-09-13 07:30:29 | |
| |
| ** DENIED ** |
| |
| 1) NOTE: PLEASE DECLARE IF THIS IS A CHANGE IN |
| OCCUPANCY OR USE ON PLANS. |
| DOES NOT INDICATE THE PREVIOUS USE BEING NEW RESTAURANT |
| BUILD OUT AND APPEARS TO BE A NEW BUILD OUT OF |
| RESTAURANT. |
| |
| 2) NOTE: PLEASE INCLUDE THE ADDRESS ON THE MEP PLANS AS |
| SHOWN ON THE ARCHITECTURAL SHEETS. |
| FAC 61G15-23.002 |
| FBC 106.1.2, 110.1.2 |
| |
| 3) NOTE: PLEASE SEE THE ELECTRICAL PLANS ONLY INDICATE |
| ONE A/C SYSTEM BEING FIGURED INTO LOAD CALCULATIONS AND |
| PANEL, YET THE ARCHITECTURAL SHEET SP-1 INDICATES AN |
| EXISTING A/C SYSTEM WITH A NEW ONE BEING ADDED? NEC, |
| 220, FBC 106.3.5.1.2 |
| |
| 4) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE |
| ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY |
| CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B, |
| 13-415.1.C. |
| PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE |
| STILL REQUIRED PER 13-415.2. PLEASE SEE |
| TABLES415.2.C.1, 415.2.B.1. |
| PLEASE SUBMIT A FIXTURE LEGEND ON PLANS WITH |
| INFORMATION ON FIXTURE TYPES WATTAGE ETC. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS |
| AND SERVICE EQUIPMENT AS SHOWN ON RISER. |
| 110.9. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE: PLEASE INDICATE *FLOATING NEUTRAL* REQUIRED AT |
| THE METERS. |
| 250.6, 250.24 |
| |
| 7) NOTE: PLEASE SEE NFPA-96 FOR SHUT DOWN OF ALL |
| ELECTRICAL UNDER HOOD. |
| PLEASE INDICATE THE REQUIRED SHUNT TRIP BREAKERS. |
| PLEASE SEE CHAPTERS 9 AND 10. PLEASE BE SURE TO SEE ANY |
| MECHANICAL REVIEW COMMENTS. |
| |
| 8) NOTE: PLEASE PROVIDE THE MINIMUM ADA LEVELS FOR FIRE |
| ALARMS DEVICES PER 11-4.28.1, .2 AND .3(4). |
| |
| 9) NOTE: PLEASE CORRELATE PLANS WITH RISER. PLANS ONLY |
| INDICATE ONE METER AND ONE MAIN DISCONNECT. |
| PLEASE INCLUDE ALL EQUIPMENT AS SHOWN ON RISER ON THE |
| PLANS WITH THE LOCATIONS. |
| 100.26, FBC 106.1.2 |
| |
| 10) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING |
| STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS |
| IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN |
| EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING |
| THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS |
| THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL |
| INTEGRITY OF THE FOUNDATION. |
| (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS |
| IS BEING SPECIFIED.) |
| PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50, |
| 250.104. |
| |
| 11) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS |
| REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW |
| THIS WAS A CHANGE IN THE 2005 NEC. |
| 230.42, 215.3, 422.13 ETC |
| |
| 12) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE. |
| THE PANEL SCHEDULE SHOWS PANEL WITH A 150AMP MAIN |
| CIRCUIT BREAKER, AND RISER SHOWS THIS WITH A 200AMP |
| MAIN CIRCUIT BREAKER. |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN |
| KITCHEN AREAS ARE REQUIRED TO BE GFI/GFI PROTECTED |
| WHETHER OR NOT THESE ARE FEEDING COUNTER SPACE AREAS. |
| PLEASE KNOW THIS WOULD INCLUDE REFRIGERATION EQUIPMENT |
| ETC. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
2007-09-13 06:58:41 | 2007-09-13 06:58:41 |
| |
| IN REVIEW |
2007-09-12 20:31:36 | 2007-09-12 20:31:36 |
| |
| REVIEW TO BE COMPLETED 9/13, NOTES TO FOLLOW. |
2007-09-12 19:58:39 | 2007-09-12 19:58:39 |
| |
| REVIEW COMMENCED |
2007-09-11 20:09:20 | 2007-09-11 20:09:20 |
| |
| IN ELEC FOR REVIEW. |