2007-11-21 18:58:33 | |
| BUILDING PLAN REVIEW |
| PERMIT: 07080580 |
| ADD: 518 21ST STREET |
| CONT: WPB HOUSING AUTHORITY |
| TEL: (561)655-8530 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 2ND |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) 106.3.3* PRODUCT APPROVALS- 2004 |
| THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS FOR THE |
| ?DOORS, WINDOWS AND MULLIONS? ARE MISSING FROM THE |
| PACKAGE. |
| |
| 3) ON SHEET A-6, INDICATE WHAT MATERIAL WILL BE USED ON |
| THE WALLS AROUND THE BATHTUBS WHEN THE EXISTING |
| MATERIAL IS REMOVED. STATE IF DUROCK, GREEN BOARD OR |
| DENSE GLASS ETC. WILL BE USED. CLARIFY PER 106.1.2 |
| |
| 4)INTERIOR WALL AND CEILING FINISH SHALL HAVE A FLAME |
| SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN TABLE |
| 803.5. INDICATE ON THE PLANS THE FLAME SPREAD IN |
| ACCORDANCE WITH FBC SECTION 803. |
| |