2007-11-30 07:18:31 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| |
| 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE |
| REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE |
| WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH |
| W/M. |
| ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS |
| ONLY SHOWN ON THE HOT SUPPLY ONLY. PLEASE SHOW THE |
| WATER HAMMER ARRESTORS ON BOTH THE HOT AND COLD WATER |
| SUPPLIES TO THE WASH MACHINE. |
| |
| 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE |
| BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1. |
| PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF |
| THE BATHROOM FIXTURES. |
| ****RESPONSE NOTED, BUT THE TUB IS NOT VENTED AS SHOWN. |
| THE VENT DOWNSTREAM OF THE OF THE TUB DOES NOT VENT THE |
| TUB. IF THE TUB IS CONNECTED TO THE BRANCH LINE |
| UPSTREAM OF THE KITCHEN SINK THE PLANS WILL MEET THE |
| CODE REQUIREMENT OR A SEPARATE VENT AT THE TUB WILL BE |
| REQUIRED. |
| |
| 4. OK |
| 5. OK |
| |
| 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE |
| THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN |
| SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC |
| 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND |
| MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS |
| IMPRESSED ON EACH SHEET. |
| ****RESPONSE NOTED, BUT SHEETS P-1 & P-3 HAVE NOT BEEN |
| RESEALED AND DO NOT HAVE THE WORD "LICENSE" IMPRESSED |
| ON THE SHEETS AS REQUIRED. |
| |
| REVIEW BY KEN STEVENS |