Plan Review Notes
Plan Review Notes For Permit 07080580
Permit Number 07080580
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-30 07:18:31DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE
 REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE
 WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH
 W/M.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS
 ONLY SHOWN ON THE HOT SUPPLY ONLY. PLEASE SHOW THE
 WATER HAMMER ARRESTORS ON BOTH THE HOT AND COLD WATER
 SUPPLIES TO THE WASH MACHINE.
  
 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1.
 PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF
 THE BATHROOM FIXTURES.
 ****RESPONSE NOTED, BUT THE TUB IS NOT VENTED AS SHOWN.
 THE VENT DOWNSTREAM OF THE OF THE TUB DOES NOT VENT THE
 TUB. IF THE TUB IS CONNECTED TO THE BRANCH LINE
 UPSTREAM OF THE KITCHEN SINK THE PLANS WILL MEET THE
 CODE REQUIREMENT OR A SEPARATE VENT AT THE TUB WILL BE
 REQUIRED.
  
 4. OK
 5. OK
  
 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE
 THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN
 SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC
 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND
 MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS
 IMPRESSED ON EACH SHEET.
 ****RESPONSE NOTED, BUT SHEETS P-1 & P-3 HAVE NOT BEEN
 RESEALED AND DO NOT HAVE THE WORD "LICENSE" IMPRESSED
 ON THE SHEETS AS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]