Plan Review Notes
Plan Review Notes For Permit 07080580
Permit Number 07080580
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-12 11:02:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS D-1 & D-2 PLEASE INDICATE THE LOCATION OF THE
 EXISTING WATER HEATERS FOR EACH UNIT. SECTION 106.1.2.
  
 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE
 REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE
 WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH
 W/M.
  
 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1.
 PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF
 THE BATHROOM FIXTURES.
  
 4. SHT P-2 SANITARY RISER. A STANDPIPE IS REQUIRED FOR
 EACH WASH MACHINE PER SECTIONS 802.4 & 1002.1. PLEASE
 INDICATE THE STANDPIPE ON RISER.--A CLEANOUT IS
 REQUIRED AT THE BASE OF THE W/M STACK A MINIMUM OF 4 FT
 ABOVE THE FLOOR FOR ACCESS. SECTION 708.9. PLEASE
 INDICATE CLEANOUTS ON RISER DIAGRAM.
  
 5. SHT P-2 SANITARY RISER. THE AIR ADMITTANCE VALVES
 SHALL BE LOCATED A MINIMUM OF 4 IN. ABOVE THE FIXTURE
 DRAIN BEING VENTED. ON THE WASH MACHINES THEY SHALL BE
 LOCATED 4" ABOVE THE AIR GAP OF THE FITTING OR 4" ABOVE
 THE STANDPIPE. SECTION 917.4. PLEASE SHOW THE AAV'S
 ABOVE THE TOP OF THE STANDPIPE MIN. 4".
  
 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE
 THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN
 SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC
 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND
 MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS
 IMPRESSED ON EACH SHEET.
  