2007-10-12 11:02:22 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHTS D-1 & D-2 PLEASE INDICATE THE LOCATION OF THE |
| EXISTING WATER HEATERS FOR EACH UNIT. SECTION 106.1.2. |
| |
| 2. SHT P-2POTABLE RISER. WATER HAMMER ARRESTORS ARE |
| REQUIRED ON BOTH THE HOT & COLD WATER SUPPLY TO THE |
| WASH MACHINES. SECTION 604.9. ONLY ONE IS SHOWN AT EACH |
| W/M. |
| |
| 3. SHT P-2 SANITARY RISER. ONLY THE FIXTURES WITHIN THE |
| BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. SECTION 909.1. |
| PLEASE SHOW THE KITCHEN SINK CONNECTION DOWNSTREAM OF |
| THE BATHROOM FIXTURES. |
| |
| 4. SHT P-2 SANITARY RISER. A STANDPIPE IS REQUIRED FOR |
| EACH WASH MACHINE PER SECTIONS 802.4 & 1002.1. PLEASE |
| INDICATE THE STANDPIPE ON RISER.--A CLEANOUT IS |
| REQUIRED AT THE BASE OF THE W/M STACK A MINIMUM OF 4 FT |
| ABOVE THE FLOOR FOR ACCESS. SECTION 708.9. PLEASE |
| INDICATE CLEANOUTS ON RISER DIAGRAM. |
| |
| 5. SHT P-2 SANITARY RISER. THE AIR ADMITTANCE VALVES |
| SHALL BE LOCATED A MINIMUM OF 4 IN. ABOVE THE FIXTURE |
| DRAIN BEING VENTED. ON THE WASH MACHINES THEY SHALL BE |
| LOCATED 4" ABOVE THE AIR GAP OF THE FITTING OR 4" ABOVE |
| THE STANDPIPE. SECTION 917.4. PLEASE SHOW THE AAV'S |
| ABOVE THE TOP OF THE STANDPIPE MIN. 4". |
| |
| 6. THE SEAL FOR THE PROFESSIONAL ENGINEER SHALL INCLUDE |
| THE WORD "LICENSE" IN THE SEAL. PLANS SEALED BY JOHN |
| SYLVIA DO NOT INDICATE "LICENSE" ON THE SEAL. FAC |
| 61G15-23.001 & FS 471.025. PLEASE RESEAL THE SHEETS AND |
| MAKE SURE ALL INFORMATION REQUIRED ON THE SEAL IS |
| IMPRESSED ON EACH SHEET. |
| |