2007-09-11 16:30:49 | ** REDLINED** | | | | 1) BEDROOM THREE: VIF IF CLOSET OR WALL SPACE INSIDE | | DOOR. IF WALL, NEEDS RECEPTACLE WITHIN 6FT OF DOOR PER | | 210.52. | | THIS WAS REDLINED AS TYPICAL FOR ALL UNITS. | | | | 2) THE PLANS INDICATES ONLY *WASHER* WHICH CIRCUITING | | AND PANEL SCHEDULE READS THIS AS A WASHER/DRYER COMBO. | | | | THIS WAS REDLINED AS TYPICAL FOR ALL UNITS. | | | | PLANS OK, STAMPED ELECTRICAL SHEETS. |
|