Plan Review Notes For Permit 07080521 |
Permit Number |
07080521 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-11-09 09:56:52 | ***DENIED*** | | A RESPONSE LETTER WAS ATTACHED TO THE PLANS EXLUDING | | FIRE REVIEW COMMENTS. NO CHANGES OR NOTES ADDED TO | | DRAWINGS. | | | | 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | 2) IT APPEARS THAT FIRE ALARM EQUIPMENT IS SHOWN ON | | ELECTRICAL SHEET 101. IF WORK IMPACTS EXISTING BUILDING | | FIRE PROTECTION SYSTEM, SEPARATE SHOP DRAWINGS AND | | PERMITS MAY BE REQUIRED FOR FIRE ALARM REMODEL. | | | | 3) THE EXIT DOOR FROM THE STAIRWELL WOULD SEEM TO | | OBSTRUCT THE EXTERIOR EXIT DOOR. PLEASE CLARIFY IF | | STAIR DOOR IS PROVIDED WITH A UL LISTED CLOSER THAT | | FUNCTIONS PROPERLY. | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH ALL REQUIREMENTS OF NFPA 241. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|