Plan Review Notes
Plan Review Notes For Permit 07080517
Permit Number 07080517
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-09 09:33:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS.
  
 1. SHEET A6.0 PLUMBING RISER DIAGRAM: THE BIDET IN THE
 MASTER BATH IS NOT VENTED. PER *901.2.1, VENTING
 REQUIRED.
  
 2. ENERGY CALCULATIONS WERE NOT RESUBMITTED WITH PLANS
 PLEASE RESUBMIT ENERGY CALULATIONS WITH WATER HEATING
 REQUIREMENTS PER
 CHAPTER 13 ENERGY EFFICIENCY SECTION 13-101.0 GENERAL.
 THIS CODE IS A STATEWIDE UNIFORM CODE AND SHALL NOT BE
 MADE MORE STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE
 CODE PROVIDES FOR A UNIFORM STANDARD OF ENERGY
 EFFICIENCY BY, AT A MINIMUM, SETTING FORTH MINIMUM
 REQUIREMENTS FOR EXTERIOR ENVELOPES, LIGHTING,
 ELECTRICAL DISTRIBUTION, AND SELECTION OF HEATING,
 LIGHTING, VENTILATION, AIR CONDITIONING AND SERVICE
 WATER HEATING SYSTEMS. IT SHALL APPLY TO ALL NEW
 BUILDINGS, TO ADDITIONS TO EXISTING BUILDINGS AND
 MANUFACTURED HOMES, TO RENOVATIONS TO EXISTING
 BUILDINGS, BOTH PUBLIC AND PRIVATE, WITH CERTAIN
 EXCEPTIONS, TO CHANGES OF OCCUPANCY TYPE, TO THE
 SITE-INSTALLED COMPONENTS AND FEATURES OF A
 MANUFACTURED HOMES AT THEIR FIRST SET-UP, AND TO THE
 INSTALLATION OR REPLACEMENT OF BUILDING SYSTEMS AND
 COMPONENTS WITH NEW PRODUCTS FOR WHICH THERMAL
 EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
  
 **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE
 SHEET A2.0 IS INDICATING GAS APPLIANCES.
  
 NOTE: GAS PERMIT REQUIRED. PLUMBING OR GAS CONTRACTOR
 TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]