Notes
Date Text
2007-08-23 09:38:41DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL WASTE PIPES OR TRAPS ARE SIZED ON SHEET
 A6.0 PLUMBING RISER DIAGRAM. PLEASE CORRECT THIS ON THE
 RESUBMITTAL.
  
 2. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A2.0. PER FBC-2004
 CHAPTER 1 THE CITY OF WEST PALM BEACH AMENDMENTS
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL.
  
 A} THE WASHING MACHINE AND LAUNDRY TRAY ARE BEING
 INDICATED IN THE WRONG PLACE.
  
 B} BATHROOM OFF BEDROOM 2 THE TUB/SHOWER IS
 INCORRECTLY IDENIFIED AS A SHOWER AND LOCATED IN THE
 WRONG PLACE. ALSO THE LAV IS LOCATED IN THE WRONG
 PLACE.
  
 3. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM THE
 WASHING MACHINE NEEDS A TRAP PER FBC-2004 PLUMBING,
 SECTION 1002.1 ALSO PLEASE INDICATE THE REQUIRED
 STANDPIPE FOR THE WASHING MACHINE PER FBC-2004
 PLUMBING, SECTION 802.4.
  
 4. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM MASTER
 BATH W. POOL TUB PER FBC-2004 PLUMBING, TABLE 906.1 A
 VENT IS REQUIRED FOR THE W. POOL TUB TRAP BECAUSE IT IS
 OVER 6 FEET FROM THE VENT.
  
 5. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM
 DISHWASHER DRAIN. PER FBC-2004 PLUMBING SECTION 802.1.6
 DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER. PLEASE CLARIFY HOW
 THE DISHWASHER WILL DRAIN. IF IT IS THE INTENT TO USE A
 STANDPIPE PLEASE CLEARLY INDICATE AND SIZE THE
 STANDPIPE ON THE RESUBMITTAL.
  
 6. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM POWDER
 ROOM: THE 2 INCH LOOP VENT BEING INDICATED FROM THE TOP
 OF THE WATER CLOSET IS NOT FEASIBLE OR REQUIRED. PLEASE
 DELETE THIS VENT ON THE RESUBMITTAL.
  
 **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE
 SHEET A2.0 IS INDICATING GAS APPLIANCES
  
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 END OF COMMENTS:
  