Date |
Text |
2007-08-23 09:38:41 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| LOCATIONS. |
| NOTE: NOT ALL WASTE PIPES OR TRAPS ARE SIZED ON SHEET |
| A6.0 PLUMBING RISER DIAGRAM. PLEASE CORRECT THIS ON THE |
| RESUBMITTAL. |
| |
| 2. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN ON SHEET A2.0. PER FBC-2004 |
| CHAPTER 1 THE CITY OF WEST PALM BEACH AMENDMENTS |
| SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| A} THE WASHING MACHINE AND LAUNDRY TRAY ARE BEING |
| INDICATED IN THE WRONG PLACE. |
| |
| B} BATHROOM OFF BEDROOM 2 THE TUB/SHOWER IS |
| INCORRECTLY IDENIFIED AS A SHOWER AND LOCATED IN THE |
| WRONG PLACE. ALSO THE LAV IS LOCATED IN THE WRONG |
| PLACE. |
| |
| 3. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM THE |
| WASHING MACHINE NEEDS A TRAP PER FBC-2004 PLUMBING, |
| SECTION 1002.1 ALSO PLEASE INDICATE THE REQUIRED |
| STANDPIPE FOR THE WASHING MACHINE PER FBC-2004 |
| PLUMBING, SECTION 802.4. |
| |
| 4. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM MASTER |
| BATH W. POOL TUB PER FBC-2004 PLUMBING, TABLE 906.1 A |
| VENT IS REQUIRED FOR THE W. POOL TUB TRAP BECAUSE IT IS |
| OVER 6 FEET FROM THE VENT. |
| |
| 5. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM |
| DISHWASHER DRAIN. PER FBC-2004 PLUMBING SECTION 802.1.6 |
| DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE |
| INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A |
| STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE |
| TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER |
| CONNECTION OF A FOOD WASTE GRINDER. PLEASE CLARIFY HOW |
| THE DISHWASHER WILL DRAIN. IF IT IS THE INTENT TO USE A |
| STANDPIPE PLEASE CLEARLY INDICATE AND SIZE THE |
| STANDPIPE ON THE RESUBMITTAL. |
| |
| 6. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM POWDER |
| ROOM: THE 2 INCH LOOP VENT BEING INDICATED FROM THE TOP |
| OF THE WATER CLOSET IS NOT FEASIBLE OR REQUIRED. PLEASE |
| DELETE THIS VENT ON THE RESUBMITTAL. |
| |
| **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE |
| SHEET A2.0 IS INDICATING GAS APPLIANCES |
| |
| NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- |
| TOR TO SUBMIT PLANS WITH PERMIT APPLICA- |
| TION. ALL GAS INSPECTIONS TO BE COMPLETE |
| BEFORE FINAL INSPECTION. |
| |
| END OF COMMENTS: |
| |