 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 FLORIDA STATUTES 1/2007,2004 FBC AS AMENDED, CHAPTER
 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS REFER TO SHEET A8.0.
  
 1} THERE IS NO EQUIPMENT GROUND SHOWN BEING RAN WITH
 THE FEEDER FROM PANEL "B" TO THE POOL PANEL.AN
 EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED FROM
 THE FIRST MEANS OF DISCONNECT TO THE PANEL PER 250.110,
 SIZED PER 250.122. SEE RISER DIAGRAM.
  
 2} THERE IS A 20 AMP CIRCUIT,#22, IN PANEL "A" FOR
 THE POOL LIGHTS, AND A 15 AMP CIRCUIT, NO NUMBER GIVEN,
 FOR POOL LIGHTS IN SUB PANEL"D". IT IS NOT CLEAR IF
 THIS IS A DUPLICATION OR IF THERE ARE TWO SEPARATE
 CIRCUITS FOR POOL LIGHTS. SEE ARTICLE 408.4 2005 NEC
 WHICH ASKS FOR CLARITY IN THE SCHEDULES.
  
 3} CIRCUIT # 21, PANEL "A", DINING ROOM OUTLETS, ARE ON
 A 15 AMP CIRCUIT. TO COMPLY WITH 210.52(B)(1) FOR SMALL
 APPLIANCE CIRCUITS, THIS MUST BE A 20 AMP CIRCUIT.
  
 4} CIRCUIT # 40 IN BOTH PANELS INDICATES A LOAD OF 2.3
 KW. IN VIOLATION OF 210.23, LIMITING THE CIRCUIT
 AMPACITY TO 80% OF THE CIRCUIT RATING ( AT 20 AMPS).
 LIST THE CIRCUIT RATING AND CONDUCTOR SIZE SO
 COMPLIANCE WITH 310.16 MAY BE REVIEWED. NOTE: THE HIGH
 HATS LISTED ON THOSE CIRCUITS ARE NOT REQUIRED TO BE ON
 A SEPARATE CIRCUIT AND MAY BE PUT ON OTHER LIGHTING AND
 RECEPTACLE CIRCUITS.
  
 5} LOCATE PANEL "D" ON THE PLAN. 106.3.5.4(8), FBC AS
 AMENDED.
  
 6} SHEET A2.0 INDICATES IN A NOTE THATAHU #3,IN
 "HER" CLOSET, MASTER BEDROOM, IS CEILING HUNG. SHEET M1
 SYSTEM SPECIFICATIONS INDICATE THERE IS A 30 AMP FUSE
 IN THE AIR HANDLER. OVERCURRENT PROTECTION IN A CLOTHES
 CLOSET IS IN VIOLATION OF 240.24(D). ALSO THERE IS A
 DISCONNECT IN THE CLOSET AND IT IS UNCLEAR IF IT
 CONTAINS OCP. IF THE INSTALLATION IS INTENDED TO BE IN
 THE ATTIC THAN IN THE CLOSET, RECEPTACLE PER 210.63, IS
 REQUIRED.
  
 7} THE ENGINEERSNAME ON THE PLAN PROVIDER AFFIDAVIT
 AND SEAL, IS DIFFERENT THAN THE ONE ON FILE WITH DBPR.
 PLEASE CLARIFY.
  