2007-08-21 12:41:55 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| FLORIDA STATUTES 1/2007,2004 FBC AS AMENDED, CHAPTER |
| 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| THESE COMMENTS REFER TO SHEET A8.0. |
| |
| 1} THERE IS NO EQUIPMENT GROUND SHOWN BEING RAN WITH |
| THE FEEDER FROM PANEL "B" TO THE POOL PANEL.AN |
| EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED FROM |
| THE FIRST MEANS OF DISCONNECT TO THE PANEL PER 250.110, |
| SIZED PER 250.122. SEE RISER DIAGRAM. |
| |
| 2} THERE IS A 20 AMP CIRCUIT,#22, IN PANEL "A" FOR |
| THE POOL LIGHTS, AND A 15 AMP CIRCUIT, NO NUMBER GIVEN, |
| FOR POOL LIGHTS IN SUB PANEL"D". IT IS NOT CLEAR IF |
| THIS IS A DUPLICATION OR IF THERE ARE TWO SEPARATE |
| CIRCUITS FOR POOL LIGHTS. SEE ARTICLE 408.4 2005 NEC |
| WHICH ASKS FOR CLARITY IN THE SCHEDULES. |
| |
| 3} CIRCUIT # 21, PANEL "A", DINING ROOM OUTLETS, ARE ON |
| A 15 AMP CIRCUIT. TO COMPLY WITH 210.52(B)(1) FOR SMALL |
| APPLIANCE CIRCUITS, THIS MUST BE A 20 AMP CIRCUIT. |
| |
| 4} CIRCUIT # 40 IN BOTH PANELS INDICATES A LOAD OF 2.3 |
| KW. IN VIOLATION OF 210.23, LIMITING THE CIRCUIT |
| AMPACITY TO 80% OF THE CIRCUIT RATING ( AT 20 AMPS). |
| LIST THE CIRCUIT RATING AND CONDUCTOR SIZE SO |
| COMPLIANCE WITH 310.16 MAY BE REVIEWED. NOTE: THE HIGH |
| HATS LISTED ON THOSE CIRCUITS ARE NOT REQUIRED TO BE ON |
| A SEPARATE CIRCUIT AND MAY BE PUT ON OTHER LIGHTING AND |
| RECEPTACLE CIRCUITS. |
| |
| 5} LOCATE PANEL "D" ON THE PLAN. 106.3.5.4(8), FBC AS |
| AMENDED. |
| |
| 6} SHEET A2.0 INDICATES IN A NOTE THATAHU #3,IN |
| "HER" CLOSET, MASTER BEDROOM, IS CEILING HUNG. SHEET M1 |
| SYSTEM SPECIFICATIONS INDICATE THERE IS A 30 AMP FUSE |
| IN THE AIR HANDLER. OVERCURRENT PROTECTION IN A CLOTHES |
| CLOSET IS IN VIOLATION OF 240.24(D). ALSO THERE IS A |
| DISCONNECT IN THE CLOSET AND IT IS UNCLEAR IF IT |
| CONTAINS OCP. IF THE INSTALLATION IS INTENDED TO BE IN |
| THE ATTIC THAN IN THE CLOSET, RECEPTACLE PER 210.63, IS |
| REQUIRED. |
| |
| 7} THE ENGINEERSNAME ON THE PLAN PROVIDER AFFIDAVIT |
| AND SEAL, IS DIFFERENT THAN THE ONE ON FILE WITH DBPR. |
| PLEASE CLARIFY. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |